Outdoor Air Temperature (OAT) Sensor —
The OAT is factory--mounted in the EconoMi$er
R
2 (FIOP
or accessory). It is a nominal 10k ohm thermistor attached
to an eyelet mounting ring.
EconoMi$er2 —
The PremierLink
t
controller is used with EconoMi$er2
(option or accessory) for outdoor air management. The
damper position is controlled directly by the PremierLink
controller; the EconoMi$er2 unit has no internal logic
device.
Outdoor air management functions can be enhanced with
field--installation of these accessory control devices:
Enthalpy control (outdoor air or differential sensors)
Space CO
2
sensor
Outdoor air CO
2
sensor
Refer to Table 22 on page 45 for accessory part numbers.
Field Connections
Field connections for accessory sensor and input devices
are made at the 16--pole terminal block (TB1) located on
the control box bottom shelf in front of the PremierLink
controller (see Fig. 50). Some input devices also require a
24--vac signal source; connect at CTB terminal R at
“THERMOSTAT” connection strip for this signal source.
See connections figures on following pages for field
connection locations (and for continued connections at the
PremierLink board inputs).
Table 23 (on page 46) provides a summary of field
connections for units equipped with Space Sensor. Table 24
(on page 46) provides a summary of field connections for
units equipped with space thermostat.
Space Sensors —
The PremierLink controller is factory--shipped configured
for Space Sensor Mode. A Carrier T--55 or T--56 space
sensor must be used. T--55 space temperature sensor
provides a signal of space temperature to the PremierLink
controller. T--56 provides same space temperature signal
plus it allows for adjustment of space temperature
setpoints from the face of the sensor by the occupants.
2
3
4
5
6
1
SW1
SEN
BRN (GND)
BLU (SPT)
RED(+)
WHT(GND)
BLK(-)
CCN COM
SENSOR WIRING
C08201
Fig. 51 -- T--55 Space Temperature Sensor Wiring
Connect T--55:
See Fig. 51 for typical T--55 internal
connections. Connect the T--55 SEN terminals to TB1
terminals 1 and 3 (see Fig. 52).
SEN
J6-7
J6-6
1
3
TB1
PL
SEN
C08212
Fig. 52 -- PremierLink Controller T--55 Sensor
Connect T--56:
See Fig. 53 for T--56 internal connections.
Install a jumper between SEN and SET terminals as
illustrated. Connect T--56 terminals to TB1 terminals 1, 3
and 5 (see Fig. 54).
2
3
4
5
6
1
SW1
SEN
SET
Cool
Warm
BRN (GND)
BLU (SPT)
RED(+)
WHT(GND)
BLK(-)
CCN COM
SENSOR WIRING
JUMPER
TERMINALS
AS SHOWN
BLK
(T56)
C08202
Fig. 53 -- T--56 Internal Connections
SEN
J6-7
J6-6
1
3
TB1
PL
SEN
SET
Jumper
TB1
PL
J6-5
5
SET
C08213
Fig. 54 -- PremierLink Controller T--56 Sensor
Connect Thermostat —
A 7--wire thermostat connection requires a 24--v power
source and a common connection. Use the R and C
terminals on the CTB’s THERMOSTAT connection strip
for these. Connect the thermostat’s Y1, Y2, W1, W2 and
G terminals to the PremierLink controller at TB1 as
shown in Fig. 55.
If the 50TCQ unit is equipped with factory--installed smoke
detector(s), disconnect the factory BLU lead at TB1--6 (Y2)
before connecting the thermostat. Identify the BLU lead
originating at CTB--DDC--1; disconnect at TB1--6 and tape
off. Confirm that the second BLU lead at TB1--6 remains
connected to the PremierLink controller at J4--8.
Содержание 50TCQD
Страница 5: ...5 C14192 Fig 2 Unit Dimensional Drawing 14 Size Unit ...
Страница 6: ...6 C14193 Fig 2 Unit Dimensional Drawing 14 Size Unit cont ...
Страница 10: ...10 C10365 Fig 6 Roof Curb Details ...
Страница 17: ...17 a50 9707 Fig 26 Typical 50TCQ Control Wiring Diagram ...
Страница 18: ...18 a50 9708 Fig 27 Typical 50TCQ Power Wiring Diagram 208 230V 3 Phase 60Hz unit shown ...
Страница 43: ...43 a50 9710 Fig 50 PremierLinkt Controller Wiring Schematic ...
Страница 51: ...51 a50 9711 Fig 66 RTU Open Controller System Wiring Diagram ...