29
DIP
Switch
Label
DIP
Switches
(3)
S-Bus
2 Pin Side
Connector
S-Bus
Terminals
(1 and 2)
C14157
Fig. 44 -- S--Bus Sensor DIP Switches
Table 9 – Enthalpy Control Sensor Wiring Terminations*
Terminal
Type
Description
Nbr
Label
1
S---BUS
S---BUS
S---Bus Communications
(Enthalpy Control Sensor Bus)
2
S---BUS
S---BUS
S---Bus Communications
(Enthalpy Control Sensor Bus)
* Terminals are polarity insensitive.
Table 10 – Enthalpy Control Sensor DIP Switch Settings
Use
DIP Switch Positions for Switches 1, 2, and 3
1
2
3
DA*
OFF
ON
OFF
RA
[
ON
OFF
OFF
OA**
OFF
OFF
OFF
* DA = Discharge Air
[
RA = Return Air
** OA = Outside Air
NOTE
: When a S--Bus sensor is connected to an existing
network, it will take 60 minutes for the network to
recognize and auto--configure itself to use the new sensor.
During the 60 minute setup period, no alarms for sensor
failures (except SAT) will be issued and no economizing
function will be available.
CO
2
Sensor Wiring —
When using a CO
2
sensor the black and brown common
wires are internally connected and only one is connected
to “IAQ COM” on the W7220. Use the power from the
W7220 to power the CO
2
sensor OR make sure the ground
for the power supplies are common. See Fig. 45 for CO
2
sensor wiring.
CO
2
SENSOR
24V
ANALOG
OUT
L1
(HOT)
L2
RED
BLACK
YELLOW
BROWN
ORANGE
GREEN
+
–
POWER SUPPLY. PROVIDE DISCONNECT
MEANS AND OVERLOAD PROTECTION
AS REQUIRED.
1
1
C14158
Fig. 45 -- Wiring for CO
2
Sensor
Interface Overview
This section describes how to use the economizer’s user
interface for:
S
Keypad and menu navigation
S
Settings and parameter changes
S
Menu structure and selection
User Interface —
The user interface consists of a 2--line LCD display and a
4--button keypad on the front of the economizer controller.
2 LINE
LCD
MENU UP
(EXIT)
BUTTON
SCROLL
UP/DOWN
BUTTONS
SELECT
(ENTER)
BUTTON
C14206
Fig. 46 -- W7220 Controller
Keypad —
The four navigation buttons (see Fig. 46) are used to scroll
through the menus and menu items, select menu items,
and to change parameter and configuration settings.
Содержание 50TCQD
Страница 5: ...5 C14192 Fig 2 Unit Dimensional Drawing 14 Size Unit ...
Страница 6: ...6 C14193 Fig 2 Unit Dimensional Drawing 14 Size Unit cont ...
Страница 10: ...10 C10365 Fig 6 Roof Curb Details ...
Страница 17: ...17 a50 9707 Fig 26 Typical 50TCQ Control Wiring Diagram ...
Страница 18: ...18 a50 9708 Fig 27 Typical 50TCQ Power Wiring Diagram 208 230V 3 Phase 60Hz unit shown ...
Страница 43: ...43 a50 9710 Fig 50 PremierLinkt Controller Wiring Schematic ...
Страница 51: ...51 a50 9711 Fig 66 RTU Open Controller System Wiring Diagram ...