38
Table 17 – Dry Bulb Operation No DCV (CO
2
Sensor) -- 2 Speed Fan
Demand
Controlled
Ventilation
(DCV)
Outside Air ---
Good to
economize?
Y1
I
Y2-I
Fan Speed
Y1-O
Y2-O
Occupied
Unoccupied
None
No
Off
Off
Low
0-v/Off
0-v/Off
MIN POS L
Closed
On
Off
Low
24-v/On
0-v/Off
MIN POS L
Closed
On
On
High
24-v/On
24-v/On
MIN POS H
Closed
None
Yes
Off
Off
Low
0-v/Off
0-v/Off
MIN POS L
Closed
On
Off
Low
0-v/Off
0-v/Off
MIN POS L to Full-Open
Closed to Full-Open
On
On
High
DELAY
[
24-v/On
0-v/Off *
MIN POS H to Full-Open
Closed to Full-Open
*
With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on second stage of mechanical cooling Y2 –O after the delay if the call for Y1---I and Y2---I
have not been satisfied.
[
With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is a delay for the high speed fan to try to satisfy the call for second
stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage mechanical cooling is enabled.
Table 18 – Dry Bulb Operation With DCV (CO
2
Sensor) -- 2 Speed Fan
Demand
Controlled
Ventilation
(DCV)
Outside Air ---
Good to
economize?
Y1
I
Y2-I
Fan Speed
Y1-O
Y2-O
Occupied
Unoccupied
Below set
No
Off
Off
Low
0-v/Off
0-v/Off
VENTMIN L
Closed
On
Off
Low
24-v/On
0-v/Off
VENTMIN L
Closed
On
On
High
24-v/On
24-v/On
VENTMIN H
Closed
Yes
Off
Off
Low
0-v/Off
0-v/Off
VENTMIN L
Closed
On
Off
Low
0-v/Off
0-v/Off
VENTMIN L to Full-Open
Closed to Full-Open
On
On
High
24-v/On
0-v/Off*
VENTMIN H to Full-Open
Closed to Full-Open
Above set
No
Off
Off
Low
0-v/Off
0-v/Off
VENTMIN L to VENTMAX
Closed
On
Off
Low
24-v/On
0-v/Off
VENTMIN L to VENTMAX
Closed
On
On
High
24-v/On
24-v/On
VENTMIN H to VENTMAX
Closed
Yes
Off
Off
Low
0-v/Off
0-v/Off
VENTMIN L to VENTMAX
Closed
On
Off
Low
0-v/Off
0-v/Off
VENTMIN L to Full-Open
Closed to Full-Open
On
On
High
DELAY
[
24-v/On
0-v/Off *
VENTMIN H to Full-Open
Closed to Full-Open
*
With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on second stage of mechanical cooling Y2 –O after the delay if the call for Y1---I and Y2---I
have not been satisfied.
[
With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is a delay for the high speed fan to try to satisfy the call for second
stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage mechanical cooling is enabled.
Содержание 50TCQD
Страница 5: ...5 C14192 Fig 2 Unit Dimensional Drawing 14 Size Unit ...
Страница 6: ...6 C14193 Fig 2 Unit Dimensional Drawing 14 Size Unit cont ...
Страница 10: ...10 C10365 Fig 6 Roof Curb Details ...
Страница 17: ...17 a50 9707 Fig 26 Typical 50TCQ Control Wiring Diagram ...
Страница 18: ...18 a50 9708 Fig 27 Typical 50TCQ Power Wiring Diagram 208 230V 3 Phase 60Hz unit shown ...
Страница 43: ...43 a50 9710 Fig 50 PremierLinkt Controller Wiring Schematic ...
Страница 51: ...51 a50 9711 Fig 66 RTU Open Controller System Wiring Diagram ...