8.9 - Prioritisation
No. Description
Setting
Unit
Display conditions
Access
level
Min.
Max.
Increment
902 Heat recovery unit operation start cooling
percentage
0
P903
1
%
2
903 Heat recovery unit operation end cooling percentage
P902
100
1
%
2
904 Coil 1 operation start cooling percentage
0
P905
1
%
P28 Water coil no.1 = Cooling
or Mixed
2
905 Coil 1 operation end cooling percentage
P904
100
1
%
P28 Water coil no.1 = Cooling
or Mixed
2
906 Hydraulic coil 2 operation start cooling percentage
0
P907
1
%
P29 Water coil no.2 = Cooling or
Mixed
2
907 Hydraulic coil 2 operation end cooling percentage
P906
100
1
%
P29 Water coil no.2 = Cooling or
Mixed
2
920 Heat recovery unit operation start heating
percentage
0
P921
1
%
2
921 Heat recovery unit operation end heating percentage P920
100
1
%
2
924 Coil 1 operation start heating percentage
0
P925
1
%
P28 Hydraulic coil no.1 = Heating
or Mixed
2
925 Coil 1 operation end heating percentage
P924
100
1
%
P28 Hydraulic coil no.1 = Heating
or Mixed
2
926 Hydraulic coil 2 operation start heating percentage
0
P927
1
%
P29 Water coil no.2 = Heating or
Mixed
2
927 Hydraulic coil 2 operation end heating percentage
P926
100
1
%
P29 Water coil no.2 = Heating or
Mixed
2
930 Electric heater operation start heating percentage
0
P931
1
%
P32 Electric heater = 1 on/off
stage
or 2 on/off stages
or 1 gradual stage
or 1 gradual stage and 1 on/off
stage
2
931 Electric heater operation end heating percentage
P930
100
1
%
P32 Electric heater = 1 on/off
stage
or 2 on/off stages
or 1 gradual stage
or 1 gradual stage and 1 on/off
stage
2
941 Electric heater stage 1 range end percentage
0
P942
1
%
P32 Electric heater = 1 on/off
stage
or 2 on/off stages
or 1 gradual stage
or 1 gradual stage and 1 on/off
stage
2
942 Electric heater stage 2 range end percentage
P941
P943
1
%
P32 Electric heater = 2 on/off
stages
or 1 gradual stage and 1 on/off
stage
2
943 Electric heater stage 3 range end percentage
P942
100
1
%
P32 Electric heater = 2 On/Off
stages
2
8.10 - Intake FMA EC motor
No. Description
Setting
Unit
Display conditions
Access
level
Min.
Max.
Increment
1200 Min. speed percentage
0
P1201
1
%
3
1201 Max. speed percentage
P1200
100
1
%
3
8.11 - Exhaust FMA EC motor
No. Description
Setting
Unit
Display conditions
Access
level
Min.
Max.
Increment
2200 Min. speed percentage
0
P2201
1
%
3
2201 Max. speed percentage
P2200
100
1
%
3
8 - PARAMETERS
61
Содержание 39HXC
Страница 1: ...C O N T R O L S M A N U A L Translation of the original document 39HXC 39HXE 39HXV ...
Страница 2: ...2 ...
Страница 62: ...62 ...
Страница 63: ...63 ...