8.4 - Versions
No.
Description
Access level
551
AHU software version
1
552
AHU Bios version
1
553
AHU boot version
1
556
SO number
3
8.5 - Fault level
No. Description
Setting
Display conditions
Access
level
Enumeration
By default
602
Air intake filter 1 fouled
0: Maintenance
1: Danger
0
2
606
Exhaust filter 1 fouled
0: Maintenance
1: Danger
0
2
609 Electric heater safety thermostat
0: Maintenance
1: Danger
0
P32 Electric heater = 1 on/off stage
or 2 on/off stages
or 1 gradual stage
or 1 gradual stage and 1 on/off stage
or
P31 Electric preheater = with
3
615 rotary heat exchanger
0: Maintenance
1: Danger
0
P36 Heat recovery unit = Gradual speed
heat recovery unit
2
620 Supply air temperature too low
0: Maintenance
1: Danger
0
2
621 Supply air temperature too high
0: Maintenance
1: Danger
0
2
622 Return temperature too low
0: Maintenance
1: Danger
0
P146 Target temperature selection = return
air
2
623 Return temperature too high
0: Maintenance
1: Danger
0
P146 Target temperature selection = return
air
2
624 Room temperature too low
0: Maintenance
1: Danger
0
P146 Target temperature selection = room
2
625 Room temperature too high
0: Maintenance
1: Danger
0
P146 Target temperature selection = room
2
628 supply air duct pressure too low
0: Maintenance
1: Danger
0
P104 Air intake ventilation control = Duct
pressure
2
629 supply air duct pressure too high
0: Maintenance
1: Danger
0
P104 Air intake ventilation control = Duct
pressure
2
632 Loss of communication with energy meter
0: Maintenance
1: Danger
0
P44 Energy meter = With
2
635 Loss of communication with Th Tune
0: Maintenance
1: Danger
0
P149 = with
2
636 Loss of communication with the heat recovery
unit outlet sensor, intake side
0: Maintenance
1: Danger
0
P38 Temperature sensor upstream of heat
recovery unit = With
2
640 room temperature sensor
0: Maintenance
1: Danger
0
P149 = with
2
642 energy meter
0: Maintenance
1: Danger
0
P44 Main unit energy meter = With
2
650 Coil 1 pump fault
0: Maintenance
1: Danger
0
P92 Coil no. 1 pump = with
2
651 Coil 2 pump fault
0: Maintenance
1: Danger
0
P93 Coil no. 2 pump = with
2
652 exhaust duct pressure too low
0: Maintenance
1: Danger
0
P105 Exhaust ventilation control = Duct
pressure
2
653 exhaust duct pressure too high
0: Maintenance
1: Danger
0
P105 Exhaust ventilation control = Duct
pressure
2