5.2 - Modbus TCP/IP and BACnet IP
Configuring the board
Status LED
MAC address
Ethernet LED
Pushbutton
Earth connector
The board is factory fitted. If this is not the case, switch off the controller and insert the board in J13 (entitled BMS card or BMS1) on
the controller.
Press the button found on the board whilst switching the power to the controller back on. The left-hand LED will start to flash rapidly.
Keep pressing the reset button. After approximately 8 seconds, the left-hand LED (status LED) changes from green to red,
and then starts flashing. At this point, release the button.
Powered up
Release the button
Button pressed
Button
Button
Approx 8 s
Button released
Red
Green
The board is now initialised to the address 172.16.0.1. You will now need to configure your PC to a fixed IP.
Procedure for Windows 7:
Important: you must have administrator rights to your computer
Go to the
Start
menu on your PC then
Control Panel
.
In the Network and Internet section, click the link
View network status and tasks
.
5 - CONNECTION TO A CMS