8.6 - Communication parameters
No. Description
Setting
Display conditions
Access
level
Enumeration
By default
BMS1
700 Selection of the type of communication
protocol used on the BMS1 port
0: None
1: MODBUS RTU
2: LON
3: KNX
4: MODBUS TCP
5: BACNET IP
6: WEB
0
2
701 Selection of the transmission speed on the
BMS1 port
0: 1200
1: 2400
2: 4800
3: 9600
4: 19200
3 if P700=1 or 3
2 if P700=2
4 if P700=4, 5 or 6
P700 = 1
2
702 Parity on the BMS1 port
0: without
1: even
2: odd
0
P700 = 1
2
703 Number of stop bits on the BMS1 port
1
P700 = 1
2
705 Selection of the controller address on the
BMS1 bus
1
P700 = 1
2
706 Control type
0: Local
1: Remote
0
2
port
710 Selection of the type of communication
protocol used on the BMS2 port
1: ModBus RTU
0
2
711 Selection of the transmission speed on the
BMS2 port
0: 1200
1: 2400
2: 4800
3: 9600
4: 19200
3
2
712 Parity on the BMS2 port
0: without
1: even
2: odd
0
2
713 Number of stop bits on the BMS2 port
1
2
715 Selection of the controller address on the
BMS2 bus
1
2
716 Control type
0: Local
1: Remote
0
2
pLAN
720 pCO address on the pLAN network
1
8.7 - Calibration
No. Description
Setting
Unit
Display conditions
Access
level
Min.
Max.
800
Calibration of the air intake fan flow rate sensor
3
801
Calibration of the air extraction fan flow rate sensor
3
802 Intake duct pressure sensor calibration
P104 Air intake ventilation control =
Duct pressure
3
803 Exhaust duct pressure sensor calibration
P104 Intake ventilation control =
Duct pressure
and
P105 Exhaust ventilation control =
Duct pressure
3
804
Intake filter differential pressure
3
805
Exhaust filter differential pressure
3
808 Supply air duct temperature sensor calibration
-5.0
5,0
°C
Sensor present
3
809 Internal supply air temperature sensor calibration
-5.0
5,0
°C
3
810 Calibration of fresh air temperature sensor
-5.0
5,0
°C
3
811 Return air temperature sensor calibration
-5.0
5,0
°C
3
813 Calibration of the room air temperature sensor
-3.0
3,0
°C
P149 = with in read-only, modifiable
from Th-Tune
3
814 Calibration of the heat recovery unit outlet
temperature sensor, intake side
-3,0
3,0
°C
P38 Temperature sensor upstream of
heat recovery unit = With
3
816 Calibration of CO
2
Air Quality sensor
-200
200
ppm
P149 Air quality control = With
3
817 Heat recovery unit DP pressure sensor calibration
P37 Differential pressure sensor on the
heat recovery unit = With
3
8 - PARAMETERS
59
Содержание 39HXC
Страница 1: ...C O N T R O L S M A N U A L Translation of the original document 39HXC 39HXE 39HXV ...
Страница 2: ...2 ...
Страница 62: ...62 ...