No. Description
Setting
Unit
Display conditions
Access
level
Enumeration
Min.
Max.
Increment
410 Stage 1 electric heater
0: off
1: on
0
1
1
P32 Electric heater = 1 on/off
stage
or 2 on/off stages
or 1 gradual stage
or 1 gradual stage + 1 on/off stage
1
411 Stage 1 electric heater operating-
hour meter
0
999999,9
0,1
h
P32 Electric heater = 1 on/off
stage
or 2 on/off stages
or 1 gradual stage
or 1 gradual stage + 1 on/off stage
1
412 Gradual electric heater stage
percentage
0
100
1
%
P32 Electric heater =
1 gradual stage
or 1 gradual stage and 1 on/off
stage
1
414 Stage 2 electric heater
0: off
1: on
0
1
1
P31 Electric preheater = with
or
(P32 Electric heater = 2 on/off
stages
or 1 gradual stage + 1 on/off
stage)
1
415 Stage 2 electric heater operating-
hour meter
0
999999,9
0,1
h
P31 Electric preheater = with
or
(P32 Electric heater = 2 on/off
stages
or 1 gradual stage + 1 on/off
stage)
1
420 Electric heater load shedding
status
0: inactive
1: active
0
1
1
(P32 Electric heater = 1 on/off
stage
or 2 on/off stages
or 1 gradual stage
or 1 gradual stage + 1 on/off
stage)
1
421 Electric preheater load shedding
status
0: inactive
1: active
0
1
1
P31 = with
422 Changeover status
0: heating
1: cooling
0
1
1
P28 Coil no.1 = mixed or
P29 Coil no.2 = mixed
1
424 Pump 1
0: off
1: on
0
1
1
P92 Coil 1 pump = With
1
425 Pump 1 operating-hour meter
0
999999,9
0,1
h
P92 Coil 1 pump = With
1
426 Pump 2
0: off
1: on
0
1
1
P93 Coil 2 pump = With
1
427 Pump 2 operating-hour meter
0
999999,9
0,1
h
P93 Coil 2 pump = With
1
430 External generator run order
0: off
1: on
0
1
1
P90 External generator = heater
or cooler
1
451 Heat recovery unit operating-hour
meter
0
999999,9
0,1
h
P36 Heat recovery unit = Gradual
speed heat recovery unit
1
452 Heat recovery unit speed
percentage
0
100
1
%
P36 Heat recovery unit = Gradual
speed heat recovery unit
1
453
Recovery unit efficiency
0
100
1
%
P38 Temperature sensor upstream
of heat recovery unit = Without
1
454 Heat recovery unit instantaneous
efficiency
0
100
1
%
P38 Temperature sensor upstream
of heat recovery unit = With
1
456 Heat recovery unit bypass opening
percentage
0
100
1
%
P36 Heat recovery unit = Plate
1
470 Maintenance faults summary
0: off
1: on
0
1
1
1
471 Danger fault summary
0: off
1: on
0
1
1
1
490 Weekly programming request
0: inactive
1: active
0
1
1
1
491 State requested by the weekly
programming
0: Off
1: Frost protection
2: Night cool
3: Setpoint 2 on
5: On
0
5
1
1
492 Annual programming request
0: inactive
1: active
0
1
1
1
493 State requested by the annual
programming
0: Off
1: Frost protection
2: Night cool
3: Setpoint 2 on
5: On
11: Weekly prog. 1
12: Weekly prog. 2
13: Weekly prog. 3
14: Weekly prog. 4
15: Weekly prog. 5
16: Weekly prog. 6
0
16
1
1