Installation Instructions
Tighten torque N·
m
Shaft (valve body)
Cap (cover)
T-shape nut (check joint)
For gas pipe
Less than 7
Less than 30
13
For liquid pipe
7.85 (MAX15.7)
29.4 (MAX39.2)
8.8 (MAX14.7)
12
Because the unit is with refrigerant R410A, the below issues should be carefully noted:
• To prevent a different oil from entering the pipe, please use the special tool prescribed for R410A,
especially for gauge manifold and charging hose.
• To prevent the compressor oil from entering the refrigerant cycle, please use the anti-counter-flow adapter.
(8). Check valve operation
Open/close method:
• Remove the valve cap.
• Turn the liquid stop valve and the gas stop valve with a hexangular spanner until it stops. If the valve is
opened aggressively, it will be damaged.
• Tighten the valve cap.
Tighten torque as shown in the table below:
(9). Additional refrigerant charging
Charge the additional refrigerant in liquid state with the gauge.
If the additional refrigerant cannot be charged fully when the outdoor unit is off, charge it during trial. If the unit runs for a
long period without refrigerant, the compressor will fail.
(charging must be finished within 30 minutes, especially when the unit is running).
A. The unit is only charged with the standard volume of refrigerant (distributing pipe length is 0 m). Additional
charging amount=actual length of liquid pipe x additional amount per meter liquid pipe
Additional charging amount=L1×0.35+L2×0.25+L3×0.17+L4×0.11+L5×0.054+L6×0.022
L1: total length of 22.22 liquid pipe; L2: total length of 19.05 liquid pipe; L3: total length of 15.88 liquid
pipe; L4: total length of 12.7 liquid pipe; L5: total length of 9.52 liquid pipe; L6: total length of 6.35 liquidpipe;
B. Refrigerant charging and additional charging
Note:
• To prevent a different oil from entering the pipe, please use the special tool for R410A, especially for gauge manifold
and charging hose.
• Mark the refrigerant type in a different colour on the tank. R410A is pink.
• When charging refrigerant, it should be taken out from the tank in liquid state.
• Mark the refrigerant volume according to the distributing pipe length on the label.
Additional refrigerant charging per meter(kg/m
)
Charging outside the factory
Ø
22.22
Ø
19.05
Ø
15.88
Ø
12.7
Ø
9.52
Ø
6.35
0.35
0.25
0.17
0.11
0.054
0.022
Refer to label
GWP: 2088
The product contains fluorinated greenhouse gases and its functioning relies on such gases.
Model
Sound power level(dBA)
Shipping
Weight
(kg)
Cooling
Heating
38VS125C7SHQEE
69
71
97
38VS140C7SHQEE
71
73
97
12
English
Содержание 38VS125C7SHQEE
Страница 35: ...The manufacturer reserves the right to change any product specifications without notice ...
Страница 66: ...Il produttore si riserva il diritto di modificare le specifiche del prodotto senza preavviso ...
Страница 97: ...Le fabricant se réserve le droit de modifier les spécifications du produit sans préavis ...
Страница 128: ...Der Hersteller behält sich das Recht vor Produktspezifikationen ohne Vorankündigung zu ändern ...
Страница 159: ...El fabricante se reserva el derecho de modificar las especificaciones del producto sin previo aviso ...
Страница 190: ...O fabricante reserva se o direito de alterar qualquer especificação de produtos sem aviso prévio ...