F_19: Multifunctional input terminal 1 function = 1~5
(1~6:CPU version v1.9 and above)
F_20: Multifunctional input terminal 2 function = 1~ 5
(1~6:CPU version v1.9 and above)
1. F_19=1 or F_20 =1: JO
G
control (refer to F_09)
2. F_19, F_20 =2 or 6 Multi-speed control:
F_19=2 & F_20=6:
TM2 SP1 Terminal
TM2 RESET Terminal
Output frequency
ON
OFF
F_08
OFF
ON
F_26
ON
ON
F_27
F_19=6 & F_20=2:
TM2 SP1 Terminal
TM2 RESET Terminal
Output frequency
ON
OFF
F_26
OFF
ON
F_08
ON
ON
F_27
NOTE: F_19,F_20=2 or 6 are new function for CPU version v1.9 and above.
3. F_19, F_20 =3: External emergency stop
When the external emergency stop signal is activated, the inverter proceeds to decelerate
and stop, (ignoring the setting of F_14). The inverters E.S. light will flash after stopping.
After the emergency stop signal is deactivated, turn the RUN switch OFF and then ON
again to cycle it. (F_10=1) Or, push the RUN key (F_10=0). The inverter will then resume
operation and restart. If the emergency stop signal is removed before the inverter stops,
the inverter will still execute the emergency stop.
4. F_19, F_20 =4: External Base Block (Immediate Shut Down)
When the external base block signal is activated, the inverter output will be immediately
shut off (ignoring the setting of F_14) and flash b.b. Light. After the base block signal is
deactivated, turn the RUN switch OFF and then ON again (F_10=1) or push the RUN key
(F_10=0), the inverter will restart from the original starting frequency.
Time
Run/Stop
F_19=3
ON
OFF
ON
OFF
ON
F_02
RVDF Advanced User Manual