28
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 23/03/2011
F_06: frequency upper limit range=1~120Hz
F_07: frequency lower limit range=1~120Hz
(1~200Hz with CPU versionv1.9 and above)
F_06: Factory setting refers to F_25.
nal
ency
al
(NOTE)
Frequency
s
etting
s
ignal
F_06 (fre
q
. Upper limit)
F_07 (fre
q
. Lower limit)
NOTE:
If F_07 = 0 Hz,
If the frequency instruction is equal to 0Hz, the inverter will stop
at 0 speed.
If F_07 > 0 Hz,
If the frequency instruction is lower than F_07, the inverter will output a
minimum speed according to the setting in F_07
F_08: SP1 frequency = 1 ~ 120Hz(1~200Hz:CPU version v1.9
and above)
F_09: JO
G
frequency = 1 ~ 120Hz(1~200Hz:CPU version v1.9
and above)
1. When F_19 or F_20 = 2 and the multifunction input terminal is ON, the inverter operates at sp1
frequency (F_08)
2. When F_19 or F_20 = 1 and the multifunction input terminal is ON, the inverter operate at jog
frequency (F_09)
3. The priority of reading frequency setting is: Jog
✟
Sp1
✟
Keypad setting or external frequency
signal using a speed pot.
F_10: Start / Stop Control
= 0: Keypad
= 1: Terminal (TM2)
NOTE: When F_10=1 (Terminal Control), emergency stop on the Keypad is enabled.
When F_10=1, please refer to the descriptions of F_23/24, in order to avoid the damage to
the human and the machine.
RVDF Advanced User Manual