Molded-Case Circuit Breaker / Magnetic Contact
3.5 Wiring Specification and Suitable Optionals
Model Type
RVDFA110020
RVDFA110040
RVDFA120020
RVDFA120040
RVDFA110075
RVDFB120075
RVDFB120150
RVDFB120220
RVDFB340075
RVDFB340150
RVDFB240220
Molded-case circuit breaker
15A
20A
30A
15A
Primary Circuit Terminal (TM1)
Wire dimension
(#14AWG) 2.0mm
2
Terminal screw M3
Wire dimension
(#14AWG) 2.0mm
2
Terminal screw
M3/M4
Wire dimension
3.5mm
2
Terminal screw M4
Wire dimension
3.5mm
2
Terminal screw M4
Signal Terminal (TM2)
1~11
Wire dimension 0.75mm
2
(#18 AWG), Terminal screw M3
Warrantee does not apply to damage caused by the following situations:
(1) Damage to the inverter caused by the lack of appropriate molded-case circuit breaker or when a
circuit breaker with too large of capacity is installed between the power supply and the inverter.
(2) Damage to the inverter caused by the magnetic contact, phase advancing capacitor, or surge-
protector installed between the inverter and the motor.
Use copper conductors only size field wiring based on 80°C wire only.
• Please utilize three-phase squirrel-cage induction motor with appropriate capacity.
• If the inverter is used to drive more than one motor, the total capacity must be smaller
than the capacity of the inverter. Additional thermal overload relays must be installed in
front of each motor. Use the F_18 at 1.0 times of the rated value specified on the motor
nameplate at 50Hz, 1.1 times of the rated value specified on the motor nameplate at 60Hz.
• Do not install phase advancing capacitors, LC, or RC component between the inverter
and the motor.