4.3 Parameter List
F_
Function
Function Description
Unit
Range
Factory
setting
Note
0
Factory Adjustment
0
1
Accel. Time
Accel. time
0.1s
0.1~999s
5.0
*1 *3
2
Decel. Time
Decel. time
0.1s
0.1~999s
5.0
*1 *3
3
Operation mode
0: Forward/Stop, Reverse/Stop
1: Run/Stop, Forward / Reverse
1
0~1
0
4
Motor rotation direction
0: Forward
1: Reverse
1
0~1
0
*1
5
V/F Pattern
V/F Pattern setting
1
1~6
1/4
*2
6
Frequency upper/lower limit
Frequency upper limit
0.1Hz
1.0~120Hz
(1~200) *4
50/60Hz
*3
7
Frequency lower limit
0.1Hz
0.0~120Hz
(1~200) *4
0.0Hz
*3
8
SPI frequency
SP1 frequency
0.1Hz
1.0~120Hz
(1~200) *4
10Hz
*3
9
JOG frequency
JOG frequency
0.1Hz
1.0~10.0Hz
(1~200) *4
6Hz
10
Start / Stop Control
0: Keypad
1: Terminal (TM2)
1
0~1
0
11
Frequency Control
0: Keypad
1: Terminal (0~10v / 0~20mA)
2: Terminal (4~20mA)
1
0~2
0
12
Carrier frequency control
Carrier Frequency Setting
1
1~5
(1~10)*4
5
13
Torque compensation
Torque compensation gain
0.1%
0.0~10.0%
0.0%
*1
14
Stop method
0: controlled deceleration stop
1: free run to stop
1
0~1
0
15
DC braking setting
DC braking time
0.1s
0.0~25.5s
0.5s
16
DC braking injection frequency
0.1Hz
1~10Hz
1.5Hz
17
DC braking level
0.1%
0.0~20.0%
8.0%
18
Electronic thermal
Overload protection
Protection base on motor rated
current
1%
50 ~ 100%
(0~200)*4
100%
19
Multifunction input connection
point
Multifunction input terminal 1
(SP1) function
1: Jog
2: Sp1
3: Emergency stop
4: External Base Block
5: Reset
6: SP2 *4
5
20
Multifunction input terminal 2
(RESET) function
3
21
Multi-function output
Multifunction output terminal
1: Operating
2: Frequency reached
3: Fault
3
22
Reverse Lock-Out
0: REV run
1: REV run Lock-Out
1
0~1
0
23
Momentary power loss
0: Enabled
1: Disabled
1
0~1
0
24
Auto restart
Number of Auto-restart times
1
0~5
0
25
Factory setting
010: Constants initialization to 50Hz system
020: Constants initialization to 60Hz system
*2
26
SP2 frequency
SP2 frequency
0.1Hz
1.0~200Hz
20
*4
27
SP3 frequency
SP3 frequency
0.1Hz
1.0~200Hz
30
*4
28
Direct start
0: Enabled
1: Disabled
1
0~1
0
*5
29
Software version
CPU program version
30
Fault Log
Fault log for three faults
NOTE:
*1: Indicate this parameter can be adjusted during running mode.
*2: Please refer to F_25.
*3: If the setting range is above 100, the setting unit becomes 1.
*4: New function for CPU version V1.9 and above.
*5: New function for CPU version V2.1 and above
RVDF Advanced User Manual