![CARLO GAVAZZI RVDFA110020 Скачать руководство пользователя страница 13](http://html.mh-extra.com/html/carlo-gavazzi/rvdfa110020/rvdfa110020_advanced-users-manual_2558649013.webp)
3.4.2
G
eneral Specifications
Item
Specification
Input Signal Type
PNP type (SOURCE) input (External 24VDC Input is allowed)
Control Method
Sinusoidal wave PWM control
Fr
equency Contr
ol
Freq. Range
1~200 Hz*1
Resolution Setting
Digital: 0.1 Hz (1 ~ 99.9 Hz); 1 Hz (100 ~ 200 Hz)
Analog: 1Hz/ 60 Hz
Keyboard Setting
Directly setup by
✟ ✟
buttons
External Signal Setting
0~10V, 4 ~ 20mA, 0 ~ 20mA
Other function
Frequency upper and lower limit
General Contr
ol
Carrier frequency
4~16KHz*2
Accelerate/Decelerate time 0.1~ 999 Sec
V/F Pattern
6 Patterns
Torque control
Torque boost level adjustable (manual torque boost)
Multi-Functional input
2 point, to be used as multi-speed 1(Sp.1) / multi-speed 2(Sp.2) *1/ Jog / External
emergency stop / External bb / Reset
Multi-Functional output
1a Relay terminal, to be setup as Fault / Running / Frequency.
Braking Torque
RVDFAxxxxxx series: About 20%
RVDFBxxxxxx series: 20%~100%, built-in braking transistor
Other function
Decelerate or free run stop, Auto reset, DC braking frequency / Voltage / Time can be
setup by constants
Display
Three digital LED display frequency / inverter parameter / fault record / program version
Operating temperature
-10°C ~ +40°C (without shield sticker: -10°C ~ +50°C)
Humidity
0~95% RH non-condensing
Vibration
Under 1G (9.8 m/s
2
)
EMC specification
EN61800-3+A11,EN50178
Pr
otection Function
Overload protection
150% for 1 min.
Over-voltage
DC voltage > 410V(100/200 series); DC voltage > 800V(400 series)
Under voltage
DC voltage < 200V(100/200 series); DC voltage < 400V(400 series)
Momentary Power-loss
0 ~ 2 sec: The inverter can be restarted using speed search feature
Stall Prevention
During Acceleration / Deceleration/ Constant speed
Output Short-circuit
Electronic circuitry protection
Grounding fault
Electronic circuitry protection
Other function
Heat sink overheat protection, Current limit
Installation
Mounting screw or DIN rail (only IP20 version).
12
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 23/03/2011
Note:
*1: New function for CPU version v1.9 and above.
*2: Carrier frequency range:
CPU version v1.6 is 4~8kHz.
CPU version v1.9 and above are 4~16kHz.
RVDF Advanced User Manual