“Power+” +0300050EN - rel. 2.3 - 08.06.2012

31

8. ALARMS 

8.1  Types of alarm

There are two types of alarm:

• 

drive malfunctioning alarms;

• 

motor malfunctioning alarms. 

Among the status variables it is possible to check the presence of Modbus® 
communication alarms. 

Important: 

All alarms stop the motor and must be restored using 

the alarm reset command

:

Pr.101 = 1

followed by the command:

Pr.101 = 0

to resume the initial state.

Mod. 

add.

Description

Def Min

Max

U.M. R/W

101 Reset (3 bit parameter)

The particular reset comand is executed 
when the related bit changes from 0 to 
1. After that the bit has to be cleared to 
0 again.

bit meaning

0

alarms reset and updating of 
communication parameters

1

parameters reset at default values

2

reset fl ag check drive switch on 
and switch off  (see speed register, 
bit2)

0

0

allowable 

values:

1, 2 ,4

-

R/W

Tab. 8.a 

8.2 Alarms 

log

The most recent 4 alarms are memorised in a FIFO type alarms queue. The 
last alarm memorised is visible in the Alarm 1 status variable.

Mod. 

add.

Description

Def

Min

Max

U.M.

R/W

137

Alarm 1

-

-

-

-

R

138

Alarm 2

-

-

-

-

R

139

Alarm 3

-

-

-

-

R

140

Alarm 4

-

-

-

-

R

Tab. 8.b 

8.3 Alarms 

table

The alarm code is given in the Alarm 1...4 parameters and in the alarm code 
parameter (Modbus®=105)

Alarm 

code

Description

Relay  

alarm

Reset

Possible cause

Solutions

0

No alarm 

-

-

-

-

1

Overcurrent

(*)

reset command The drive has detected a current supplied that is too 

high due to: 
- sudden strong load increase; 
- acceleration that is too high; 
- wrong parameters values  or inadequate motor.

Check the load, the dimension of the motor and 
the cables. Decrease acceleration. Check the motor 
parameters..

2

Motor overload

(*)

reset command The current supplied has exceeded the rated current  

over the maximum time accepted

3

Overvoltage 

(*)

reset command The DC voltage of the intermediate circuit has 

exceeded the limits envisioned due to: 
- deceleration that is too high; 
- high over-voltage peaks on the power supply 
network.

Decrease deceleration.

4

Undervoltage 

(*)

reset command The DC voltage of the intermediate circuit is below 

the limits envisioned due to:
- insuffi

  cient power supply voltage; 

- fault inside the drive.

In the event of temporary cut-off  of the power 
supply, reset the alarm and re-start the drive. Check 
the power supply voltage.

5

Drive overtemperature

(*)

reset command The temperature inside the drive has exceeded the 

maximum level allowed. 

Check that the quantity and fl ow of cooling air are 
regular. Check that there is not dust in the heat sink. 
Check the environment temperature. Ensure that 
the switching frequency is not too high with respect 
to the environment temperature and the motor 
load.

6

Drive undertemperature

(*)

reset command The temperature inside the drive has exceeded the 

minimum level allowed.

7

Overcurrent HW

(*)

reset command The drive has detected an istantaneous current 

supplied that is too high due to: 
- sudden strong load increase; 
- motor cables short circuit; 
- wrong parameters values  or inadequate motor.

Check the load, the dimension of the motor and the 
cables.  Check the motor parameters.

8

Motor overtemperature 

(*)

reset command The temperature detected by the PTC thermistor 

corresponds to a resistance > 2600 ohm.

Reduce the motor load. 
Check motor cooling.

9

IGBT module error

(*)

reset command Internal fault

Call for assistance

10

CPU error

(*)

reset command Loss of data in memory

Call for assistance

11

Parameter default

(*)

reset command Execution of reset parameter default command

Содержание Power+

Страница 1: ...I n t e g r a t e d C o n t r o l S o l u t i o n s E n e r g y S a v i n g s NO POWER SIGNAL CABLES TOGETHER READ CAREFULLY IN THE TEXT Power User manual Speed drive ...

Страница 2: ......

Страница 3: ...for applications other than those specified in the technical manual All of the above suggestions likewise apply to the controllers serial boards programming keys or any other accessory in the CAREL product portfolio CAREL adopts a policy of continual development Consequently CAREL reserves the right to make changes and improvements to any product described in this document without prior warning Th...

Страница 4: ......

Страница 5: ... and outputs 21 5 2 Relay configuration 21 5 3 Minimum and maximum output frequency 21 5 4 Direction of rotation inversion 21 5 5 Speed profile 21 5 6 Speed profile execution mode 22 5 7 Switching frequency 22 5 8 Stop mode 22 5 9 Flying restart 22 5 10 V f control for asynchronous motor 22 5 11 Motor control on start up 23 5 12 PI parameters 23 5 13 Commands 23 5 14 Status variables 24 5 15 Modbu...

Страница 6: ...ENG Power 0300050EN rel 2 3 08 06 2012 6 ...

Страница 7: ... the Power terminals even when this is disconnected from the power supply check the temperature of the heat sink coming in contact with the heat sink may cause burns When Power is connected to the mains motor terminals U V W are live even if the motor is not running Do not measure insulation resistance or dielectric rigidity directly on Power or with Power connected The control terminals are isola...

Страница 8: ...n control various types of compressors safety digital input Safety Torque Off dedicated input for PTC thermistor or thermostat to monitor motor overtemperature panel installation or with heat sink outside of the panel to optimize the dissipation of heat inside the electrical panel electrical connections can be made without needing to remove the plastic cover programmable acceleration curve to adap...

Страница 9: ...ype of assembly panel or with heat sink outside of the panel see the paragraph on Drilling and assembly as the position of the fastening brackets affects the total height The side brackets are only needed for assembly with the heat sink outside of the panel For single phase models the dimensions increase because the coil for power factor control circuit PFC also needs to be connected For three pha...

Страница 10: ... 5 minutes before disconnecting the electrical cables always make sure the motor has stopped completely Motors that are still freely rotating may produce dangerous voltages at the Power terminals even when this is disconnected from the power supply Description of the terminals C1 L1 L L2 N L3 U V W G F C2 E Fig 3 g Ref Description L1 L L2 N L3 Three phase power supply input earth connection L1 L L...

Страница 11: ...agnetic circuit breaker MCB is used it must be of type B rated according to the data shown in the table in paragraph 9 1 avoid installing cables connected to the control terminal block in the immediate vicinity of power devices contactors circuit breakers etc Reduce the path of the cables as much as possible and avoid spiral paths that enclose power devices Use cables rated to 90 C and if the temp...

Страница 12: ...or cable the effective switching frequency the type of earth connection used and the type of RFI filter installed If a residual current circuit breaker RCCB is to be used the following conditions apply it must be a type B device suitable to protect the equipment against leakage current with a DC component Individual RCCBs should be used for each drive Motor Connect the motor power cable use four w...

Страница 13: ... digital input Connect the Safety Torque Off digital input to a safety device for example a maximum pressure switch with normally closed voltage free contact in series with an external 24 Vac 24 Vdc voltage source without needing to observe the polarity for direct current ref A When the contact is open the drive stops operating bypassing the software control If the Safety Torque Off function is no...

Страница 14: ...ntazione power supply rettificatore rectifier induttanza PFC PFC coil DC Bus Inverter IGBT C1 L N U V W C2 1 RFI filter alimentazione power supply controllo motore motor control DSP PFC 1 3 motore motor Fig 3 s Three phase model C1 C2 ventilatore fan alimentazione power supply reattanza DC opzionale optional DC choke DC Bus Inverter IGBT L1 L3 L2 U V W 3 RFI filter rettificatore rectifiers control...

Страница 15: ...nnessione al 24 Vdc ausiliari in caso di non utilizzo della funzionalità Connection to auxiliary 24 Vdc supply when function Safety Torque Off is not used L N PE L1 L2 L3 PE Alimentaz monofase Single phase AC power supply Alimentazione trifase Three phase AC power supply PE M 3 Connessione con alimentazione di sicurezza esterna 24 Vac o 24 Vdc Connection with safety external supply 24Vac or 24Vdc ...

Страница 16: ... dissipate the heat while keeping the temperature of the plate below 70 C in the various operating conditions and that the overheating alarm does not intervene Make sure that the cooling device does not cause the formation of condensate on the inner surface of the plate Clean the contact surfaces of the Power plate and of the coldplate and ensure they couple perfectly The use of thermal compound o...

Страница 17: ...sion the space necessary for connection of the cables to the choke terminals 3 14 EMI filter The EMI filter is an optional that can be supplied separately to be used with Power drives with single phase power supply PSD00 2 0 to reduce the emissions to the levels envisioned by EN61800 3 category C1 The filter must be connected between the power supply and terminals L1 L L2 N and earth of the drive ...

Страница 18: ...20 Network address 1 247 R Tab 4 a Important the drive only reads the network address on switch on or after a reset control Dip switch address Network address Base address 1 1 0 1 1 15 16 232 0 232 232 15 247 0 15 0 15 Base address 232 Tab 4 b The address of the dip switches in the drive is set manually as indicated below 1 ON OFF 2 3 4 Fig 4 a Dip switch address Dip switches Address Dip switch 1 ...

Страница 19: ...the application with compressors the regenerative functioning mode never occurs For particular applications consult CAREL Mod add Description Def Min Max U M R W 53 Regeneration current limit 1000 100 0 0 2000 200 0 0 1 Motor rated curr R W 54 Overvoltage control current limit 100 10 0 0 2000 200 0 0 1 Motor rated curr R W Tab 4 j PI parameters for speed regulation In applications with slow accele...

Страница 20: ...cted also if its value is not used Mod add Description Def Min Max U M R W 46 Stator resistance 0 0 38500 mΩ R W Tab 4 s Motor start up These parameters optimise the initial start up phase of the motor by adapting the V f feature on the basis of the particular application in order to improve performance at low speeds Mod add Description Def Min Max U M R W 35 V f boost voltage 0 0 250 25 0 0 1 Mot...

Страница 21: ...t is possible to swap over two of U V W wires In the event of application with compressors there is only one motor rotation direction In other cases it is possible also to enable the reverse direction of rotation with the relative parameter Mod add Description Def Min Max U M R W 8 Reverse speed enable 0 1 no yes 0 0 1 R W Tab 5 c 5 5 Speed profile Power hasbeendesignedwithaprogrammablespeedprofil...

Страница 22: ...p and post ramp set points Mod add Description Def Min Max U M R W 108 Motor frequency 0 1Hz R 125 Pre ramp frequency set point 0 1Hz R 126 Post ramp frequency set point 0 1Hz R Tab 5 f 5 7 Switching frequency The parameter allows to set the switching frequency of the IGBT Insulated Gate Bipolar Transistor During functioning the switching frequency can decrease to protect the drive from overheatin...

Страница 23: ... proportional and integral the proportional action varies the control action proportionally to the error Therefore the greater the value of Kp proportional gain the faster will be the response speed The proportional action alone does not allow the set point to be reached the integral action varies the control action proportionally to the area of the error The lower the Ti integral time value the m...

Страница 24: ...put The speed register signals whether the speed profile has been completed if the speed automatic decrease function is active and with the relative flag shows whether there has been a voltage black out Other status variables inform regarding the drive temperature current voltage power supplied the energy supplied in kWh and MWh the voltage and the voltage ripple on the DC bus the number of drive ...

Страница 25: ...thin the typical values the switching frequency gradually returns to the initial value Among the reading only variables it is possible to display the effective switching frequency Mod add Description Def Min Max U M R W 24 Switching frequency 0 4kHz 1 6kHz 2 8kHz 0 0 2 R W 25 Switching frequency derating 0 1 no yes 0 0 1 R W 124 Operating switching frequency 0 4kHz 1 6Hz 2 8kHz 0 0 2 R Tab 6 b f_s...

Страница 26: ...verload protection I T current time up to 150 of the rated current for 1 minute For asynchronous motors both vector and V f control the value can normally be found on the motor technical plate For motors with permanent magnets PM it is suggested to set it at maximum motor current normally corresponding to maximum electric frequency For asynchronous motors with V f control only set the current thre...

Страница 27: ...t up Y Y Y N 23 Speed profile deceleration 60 6 0Hz s 0 500 50 0Hz s 0 1Hz s R W Set the frequency deceleration Y Y Y N 24 Switching frequency 0 0 2 R W Sets the switching frequency of the IGBT See par 6 2 0 4kHz 1 6kHz 2 8kHz Y Y Y N 25 Switching frequency derating 0 0 1 R W The function allows to automatically decrease the PWM switching frequency on the basis of drive temperature 0 disabled 1 en...

Страница 28: ...ce Ld component for motors with permanent magnets PM Ls for asynchronous motors Max PSD0 2 0 5280 528 0mH PSD0 4 0 6130 613 0mH Y Y N N 49 Leakage factor 0 0 250 0 25 R W Sets the motor dispersion factor 0 stator and rotor perfectly coupled Set at 100 0 1 N Y N N 50 Lq inductance 0 0 Depend on the model 0 1mH R W Sets the inductance component Lq per for the motor with permanent magnets PM Max PSD0...

Страница 29: ...4 R See the chapter 8 ALARMS 0 No alarm 13 Data communication fault 1 Overcurrent 14 Drive thermistor fault 2 Motor overload 15 Autotuning fault 3 Overvoltage 16 Drive disabled STO input open 4 Undervoltage 17 Motor phase fault 5 Drive overtemperature 18 Internal fan fault 6 Drive undertemperature 19 Speed fault 7 Overcurrent HW 20 PFC module error 8 Motor overtemperature 21 not used 9 IGBT module...

Страница 30: ...See par 8 4 Y Y Y 124 Operating switching frequency 0 2 R 0 4kHz 1 6kHz 2 8kHz Y Y Y 125 Pre ramp frequency set point 0 1Hz R Shows the internal set point for the output frequency before the acceleration deceleration ramps Y Y Y 126 Post ramp frequency set point 0 1Hz R Shows the internal set point for the output frequency after the acceleration deceleration ramps Y Y Y 127 RESERVED R 128 RESERVED...

Страница 31: ...tor overload reset command The current supplied has exceeded the rated current over the maximum time accepted 3 Overvoltage reset command The DC voltage of the intermediate circuit has exceeded the limits envisioned due to deceleration that is too high high over voltage peaks on the power supply network Decrease deceleration 4 Undervoltage reset command The DC voltage of the intermediate circuit i...

Страница 32: ...ion parameter 8 4 Modbus communication error code A value is memorised in the code Modbus 122 that indicates both the trend of the communication and the status of the drive These errors are not memorised in the alarms log and do not cause the activation of the alarm relay Modbus communication error Description Possible cause 1 Drive command not valid Master command not recognised by the drive 2 Ad...

Страница 33: ...ards CE conformity Low voltage directive 2006 95 EC EN 61800 5 1 Adjustable speed electrical power drive systems Safety requirements Electrical thermal and energy Electromagnetic compatibility directive 2004 108 EC EN 61800 3 ed 2 0 Adjustable speed electrical power drive systems EMC requirements and specific test methods EN61000 3 12 Electromagnetic compatibility EMC Part 3 12 Limits Limits for h...

Страница 34: ...110 110 6600 55 3300 36 7 2200 27 5 1650 22 1320 120 120 7200 60 3600 40 2400 30 1800 24 1440 130 130 7800 65 3900 43 3 2600 32 5 1950 26 1560 140 140 8400 70 4200 46 7 2800 35 2100 28 1680 150 150 9000 75 4500 50 3000 37 5 2250 30 1800 160 160 9600 80 4800 53 3 3200 40 2400 32 1920 170 170 10200 85 5100 56 7 3400 42 5 2550 34 2040 180 180 10800 90 5400 60 3600 45 2700 36 2160 190 190 11400 95 570...

Страница 35: ......

Страница 36: ...AREL INDUSTRIES HeadQuarters Via dell Industria 11 35020 Brugine Padova Italy Tel 39 049 9716611 Fax 39 049 9716600 e mail carel carel com www carel com Agenzia Agency Power 0300050EN rel 2 3 08 06 2012 ...

Отзывы: