ENG
“Power+” +0300050EN - rel. 2.3 - 08.06.2012
30
M
o
d
. add
. Parameter
Def
Min
Max
U.M.
R/W
Description
Applicable for
PM
AC
vect.
AC
V/f
108 Motor frequency
-
-
-
0.1Hz
R
Motor equivalentt frequency. Normally equal to “Post-ramp frequency
set point”, except in situations with current limitation, in which case it is
equal to the estimate value of the “Rotor frequency”
Y
Y
Y
109 Motor current
-
-
-
0.1A
R
Actual current of the motor
Y
Y
Y
110 Motor power
-
-
-
0.01kW
R
Current power of the motor
Y
Y
Y
111 Motor voltage
-
-
-
V
R
Voltage applied to the motor
Y
Y
Y
112 RESERVED
-
-
-
-
R
-
-
-
113 DC bus voltage
-
-
-
V
R
Y
Y
Y
114 Drive temperature
-
-
-
°C
R
Y
Y
Y
115 Switch-on time
-
-
-
hour
R
Drive life time
Y
Y
Y
116 Drive run time
-
-
-
hour
R
Drive switch-on time with motor running
Y
Y
Y
117 Drive run time from last
alarm
-
-
-
hour
R
Y
Y
Y
118 kWh meter
-
-
-
0.1kWh
R
Total energy supplied to the motor: when it reaches 10,000 (1000kWh),
it goes back to zero and the counter is increased in MWh
Y
Y
Y
119 MWh meter
-
-
-
MWh
R
Y
Y
Y
120 Network address
-
1
247
-
R
Drive network address
Y
Y
Y
121 Dip-switch address
-
0
15
-
R
Network address set by the drive dip-switches
Y
Y
Y
122 Modbus® communication
error
-
-
-
-
R
Show additional information regarding communication error
Y
Y
Y
123 Modbus® error counter
-
-
-
-
R
See par.8.4
Y
Y
Y
124 Operating switching
frequency
-
0
2
-
R
0 = 4kHz, 1 = 6kHz, 2 = 8kHz
Y
Y
Y
125 Pre-ramp frequency set
point
-
-
-
0.1Hz
R
Shows the internal set point for the output frequency before the
acceleration/deceleration ramps
Y
Y
Y
126 Post-ramp frequency set
point
-
-
-
0.1Hz
R
Shows the internal set point for the output frequency after the
acceleration/deceleration ramps
Y
Y
Y
127 RESERVED
-
-
-
-
R
-
-
-
128 RESERVED
-
-
-
-
R
-
-
-
129 RESERVED
-
-
-
-
R
-
-
-
130 RESERVED
-
-
-
-
R
-
-
-
131 RESERVED
-
-
-
-
R
-
-
-
132 Rotor
frequency
-
-
-
0.1Hz
R
Shows the estimated rotor frequency, expressed in equivalent
electric frequency for motors with permanent magnetic (PM) and
asynchronous motors with vector control. Shows the drive output
frequency for asynchronous motors with V/f control
Y
Y
Y
133 RESERVED
-
-
-
-
R
-
-
-
134 DCbus ripple
-
-
-
V
R
Shows the voltage variation (ripple) in the DC bus
Y
Y
Y
135 RESERVED
-
-
-
-
R
-
-
-
136 RESERVED
-
-
-
-
R
-
-
-
137 Alarm 1
-
-
-
-
R
Shows the last alarm in queue
Y
Y
Y
138 Alarm 2
-
-
-
-
R
Shows the second to last alarm in queue
Y
Y
Y
139 Alarm 3
-
-
-
-
R
Shows the third to last alarm in queue
Y
Y
Y
140 Alarm 4
-
-
-
-
R
Shows the fourth to last alarm in queue
Y
Y
Y
141 Bootloader release
-
-
-
-
R
Y
Y
Y
142 Firmware release
-
-
-
-
R
Y
Y
Y
143 Firmware checksum
-
-
-
-
R
Y
Y
Y
144 Motor control release
-
-
-
-
R
Y
Y
Y
145 Serial number 1
-
-
-
-
R
Y
Y
Y
146 Serial number 2
-
-
-
-
R
Y
Y
Y
147 Serial number 3
-
-
-
-
R
Y
Y
Y
148 Serial number 4
-
-
-
-
R
Y
Y
Y
149 Hardware Identifi cation
-
-
-
-
R
2012: PSD00122*0
2016: PSD00162*0
4014: PSD00144*0
4022: PSD00224*0
Y
Y
Y
Tab. 7.c
Содержание Power+
Страница 2: ......
Страница 4: ......
Страница 6: ...ENG Power 0300050EN rel 2 3 08 06 2012 6 ...