48
Various features
For connection utilise the MCHSMLONM Carel code that contains the connectors:
Molex® code of the contact
Ways
39-01-21220
12
39-01-2140
14
Contact code and cross section area of the connection cables to the 12 and 14 way connectors: see table
Molex® code of the contact
Permissible cable cross section area
39-00-0077
AWG16 (1.25 mm
2
)
39-00-0038
AWG 18-24 (0.25 - 0.35 mm
2
)
39-00-0046
AWG22-28 (0.22 - 0.06 mm
2
)
For crimping utilise the specific tool Molex® 69008-0724
Max number of connector connection/disconnection:
25 cycles
Maximum length of NTC probe connection cables:
50m
Maximum length of digital input connection cables:
10m
Maximum length of power output connection cables:
5m
Max. length of fan output driving connection cables:
50m
Maximum length of power supply connection cables:
3m
Protection degree (IP) of the front:
IP55
Range of storage humidity:
0 up to 80% not condensing RH
Range of working humidity:
20% up to 80% not condensing RH
Range of storage temperature:
-10 °C +70 °C
Range of functioning temp. (basic model, open air):
-10 °C +55 °C
Range of functioning temp. ( ir, open air):
-10 °C +50 ° C
Environmental pollution:
normal
Category of fire and heating resistance:
D
PTI of the insulation materials:
all the insulation materials have PTI
≥
250 v
Software class and structure:
A
Ageing period:
80000h
Installation:
Panel, see dimensions reported ono pag. 39. Fix through
the special plastic ring of the kit.
Connection:
through the four posterior connectors.
Disconnect the 12-way plug (relay) before operating on the underlying connectors (“key” and serial interface).
Always operate in the absence of power supply.
Protection against electric shock
The system consisting of the control card (MCHSML****), other optional cards (MCHSMLSERO, MCHSMLEY0,
MCHSML4200, MCHRTF***0, CONVONOFF0 and CONV0/10A0, etc.) represent a control device to be incorporated into
class I or class II equipments. The class concerning the protection against the electric shock depends on how the control
device is being integrated into the unit realised by the manufacturer. The output digital contacts (relay) are of the micro
switch type.
Turn off the power before working on the card during mounting, maintenance and replacement.
The protection against the short-circuits, owing to faulty wiring, must be guaranteed by the manufacturer of the equipment
into which the control device is being integrated.