“FCR3 three-phase controller” +030222150 - rel. 1.3 - 12.01.2021
SADRMEM
Serial address in memory
Modbus address
read/write holding register 1
resolution
and unit of me-
asure
1
range
1 to 255
default
1
Parameter in the memory used to identify the individual controller,
making it available to a supervisor network.
DELAYMEM
Response delay in memory
Modbus address
read/write holding register 2
resolution and unit of measure 1%
range
0 to 100
default
100
Parameter setting the delay in response to the control step.
0 to 100 = 0-10 sec
MAXMEM
Maximum value in memory
Modbus address
read/write holding register 3
resolution and unit of measure 1%
range
0 to 100
default
100
Parameter corresponding to the maximum output voltage value.
0 to 100 = 50-100% output
MINMEM
Minimum value in memory
Modbus address
read/write holding register 4
resolution and unit of measure 1%
range
0 to 100
default
100
Parameter corresponding to the minimum output voltage value.
0 to 100 = 0-40% output
Maximum temperature threshold
Modbus address
read/write holding register 5
resolution and unit of measure 1
range
-30 to 105°C
default
85 °C (85)
Value of the high temperature threshold
TEMPER >= then the temp. alarm (ALRTMP) is activated,
hysteresis 3°C.
TEMPALM-
Minimum temperature threshold
Modbus address
read/write holding register 6
resolution and unit of measure 1
range
-30 to 105°C
default
-20°C (148)
Value of the low temperature low threshold
TEMPER <= TEMPALM- then the temp. alarm (ALRTMP) is activated,
hysteresis 3°C.
INMEM
Input override value
Modbus address
read/write holding register 7
resolution and unit of
measure
1%
range
0 to 100
default
0
Input value for the override input option (IOVR = 1)
DELAYINMEM
Response delay
Modbus address
read/write holding register 8
resolution and unit of
measure
1%
range
0 to 100
default
100
Parameter for response delay of memory input (INMEM)
0 ÷ 100 = 0-10 sec
ALMO
Output value in the event of alarms
Modbus address
read/write holding register 9
resolution and unit of measure 1
range
0/1/2
default
0
Output value in the event of alarms
ALMO
0
0%
Off
1
50%
2
100%
OUTMEM
Output value for override
Modbus address
read/write holding register 10
resolution and unit of measure 1%
range
0 , OUTMIN to OUTMAX
default
0=Spento
Output value for the override output option (EOVR = 1)
TIMEOUTL/
TIMEOUTH
RS485 timeout value
Modbus address
read/write holding
register 11 & 12
resolution and unit of measure 1
range
0-255 HR11 / 0-5 HR12
default
30 HR11 / 0 HR12
Timeout value for the 485 serial line. After this time, the link LED goes off
and the output goes to ALMO only if input override is enabled (IOVR = 1)
TIMEOUT = TIMEOUTH*256+TIMEOUTL (seconds) (15 to 12,000)
TIMESAVE
Saving timeout value
Modbus address
read/write holding register 13
resolution and unit of measure 1
range
0-255
default
5
Timeout value for saving the values, expressed in minutes. After this time,
any parameters that have been changed are saved to memory
SADRFCR
Manual serial address
Modbus address
read input register 1
resolution and unit of
measure
1
range
1 to 255
default
R
FCR panel parameter used to identify the individual controller, making it
available to a supervisor network. – From Dip S1
DELAYFCR
Manual response delay
Modbus address
read input register 2
Delay trimmer TR3 reading
resolution and unit of
measure
1%
range
0 to 100
default
R
Parameter setting the delay in response to the control step.
0 to 100 = 0-10 sec
MAXFCR
Manual maximum value
Modbus address
read input register 3
Max. trimmer TR2 reading
resolution and unit of
measure
1%
range
0 to 100
default
R
Parameter setting the maximum output voltage value.
0 to 100 = 50-100% in uscita
MINFCR
Manual minimum value
Modbus address
read input register 4–
Min. trimmer TR1 reading
resolution and unit of measure 1%
range
0 to 100
default
R
Parameter setting the minimum output voltage value.
0 to 100 = 0-40% in uscita