14
ENG
“FCR3 three-phase controller” +030222150 - rel. 1.3 - 12.01.2021
6. FUNCTIONS
6.1 Control
mode
Control is performed based on an analogue signal (B/GND on terminal
J1) that is read by variable INFCR (IR.6). Depending on the setting of
dipswitches S2.2 and S2.3, the type of input can be selected, corresponding
to a diff erent input resistance. The hardware time constant is however the
same for each setting.
Type of input
Dipswitch S2.2
Dipswitch S2.3
Input resistance
Input constant τ
Input range
Range of variable INFCR
0/10 V input
OFF
OFF
20 KΩ
0.25 sec
0 to 5V
0 to 100 %
0/5 V input
ON
OFF
20 KΩ
0 to 10 V
0 to 100 %
0-20 mA input
ON
ON
250 Ω
0 to 20 mA
0 to 100%
Tab. 6.a
Control can also be performed based on the INMEM variable in the
memory (HR.7) by enabling input override.
The input is then fi ltered with a specifi c constant and provides the
eff ective control signal. This avoids sudden variations, even when
switching between manual and internal selection mode.
DELAY
DELAY
FCR
IN
FOR
IN (IR.10)
IN
MEM
OFF
ON
DELAY
MEM
DELAYIN
MEM
IOVR
DIPS2.1/SEL
Selezione
B
Analog Sel
Dip S2.2/S2.3
GND
0
+
–
1
1
0
Fig. 6.a
Figure 6.a shows the processing of the control signal.
The analogue signal is processed (voltage/current) based on the setting
of Dip S2.2 and S2.3 to give a range from 0 to 100. By selecting override
(IOVR), the value saved in the memory can be used instead of the
processed value.
Depending on the setting of dip S2.1 (MEM/MAM) and the override, there
are three levels of delay in response, which can be selected to manage
integration of the variable.
Par.
Modb
Range
Def
UoM
Description
Activation
INFCR
IR.6
0 .. 100
0
1%
Analogue input setting from FCR
Active when IOVR=0
INMEM
HR.7
0 .. 100
0
1%
Internal input setting from memory
Active when IOVR= 1
IOVR
CO.9
0/1
0
1
Override input
DELAYFCR
IR.2
0 .. 100
R
1%
Manual FCR delay
Active when IOVR=0 & Dip S2.1=OFF
DELAYMEM
HR.2
0 .. 100
100
1%
Memory delay
Active when IOVR=0 & Dip S2.1=ON
DELAYINMEM
HR.8
0 .. 100
100
1%
Memory delay for INMEM
Active when IOVR=1
IN
IR.10
0.100
R
1%
Processed input value
SEL
IR.1
0/1
R
1
Select settings, manual =0, internal =1
Dip S2.1
Tab. 6.b