6.2 Maximum and minimum confi guration
The minimum output voltage can be set using the MIN trimmer or
internal parameter MIN FCR. Across a range of 100%, the voltage can be
set from 0 to 40% (0-160 V @ 400V).
The same applies to the maximum voltage, set using the MAX trimmer
or internal parameter MAX FCR. Across a range of 100%, the voltage can
Dipswitches
Function
Dip S2.6
Minimum or Cut off
OFF: Minimum function
ON: Cut-off function
Tab. 6.d
Fig. 6.3.a illustrates the settings and the eff ect on the output voltage
If selecting cut-off , the control signal must be 10% for the controller to
start again.
OUT %
IN
OUTMIN
9
0
MINCUT
FCR
OFF
ON
MINCUT
MEM
DIP S2.1/SEL
MINCUT
0/OFF: Minimo
1/ON: Cut.Off
Out =
• (IN–5)+Out min
Out max – Out min
90
OUT %
IN
OUTMAX
OUTMIN
99/100
0
Out =
• IN + Out min
Out max – Out min
99
Minimo
Cut.Off
Fig. 6.c
Associated parameters
Par.
Modb
Range
Def
UoM
Description
Activation
MINCUTFCR
DI.4
0/1
0
1%
Select minimum/cut-off from Dip S2.6
Dip S2.1=OFF
MINCUTMEM
CO.4
0/1
0
1%
Select minimum/cut-off from memory
Dip S2.1=ON
SEL
IR.1
0/1
R
1
Select parameter settings, manual =0, internal =1 (S2.1)
Tab. 6.e
be set from 50% (200V @ 400V) to 100%. The choice is always set using
dipswitch S2.1 (MAN/MEM).
Fig. 6.2.a shows how the possible eff ect of the variation is processed
based on the control signal IN.
MAX
MAX
FCR
OFF
OUTMAX
50...100
0...40
OUTMIN
ON
MAX
MEM
MIN
MIN
FCR
OFF
ON
MIN
MEM
DIPS2.1/SEL
O
UT
%
I
N
MAX
O
UT
MAX
100%
99/100
50%
O
UT
%
I
N
M
I
N
40%
0%
O
UT
M
I
N
Fig. 6.b
Par.
Modb
Range
Def
UoM Description
Activation
MAXFCR
IR.3
50 .. 100 100
1%
Manual maximum setting
DIP S2.1=OFF
MINFCR
IR.4
0 .. 40
40
1%
Manual minimum setting
DIP S2.1=OFF
MAXMEM
HR.3
0 .. 40
100
1%
Internal maximum setting
Dip S2.1=ON
MINMEM
HR.4
0 .. 40
40
1%
Internal minimum setting
Dip S2.1=ON
OUTMIN
IR.7
0 .. 40
R
1%
Minimum output value
OUTMAX
IR.8
50 .. 100 R
1%
Maximum output value
SEL
DI.1
0/1
R
1
Select parameter settings, manual =0, internal =1 (Dip S2.1)
Tab. 6.c
6.3 Minimum and cut-off function
When there is no control signal, the controller may respond in two
diff erent ways
•
MINIMUM: the output voltage remains at the minimum voltage and in
practice means it never switches off .
•
CUT-OFF: the controller switches off and can only switch on again
when the control signal reaches 10%. This eff ectively means managing
the system with ON/OFF control