“FCR3 three-phase controller” +030222150 - rel. 1.3 - 12.01.2021
7. DESCRIPTION OF THE OPERATING PARAMETERS
MAC
Type of unit
Read in REPORT SLAVE ID (read-only)
Indirizzo Modbus
read input register 12
range
311
default
311
Non-modifi able parameter used to identify the type of controller for
connection to a supervisor or the programming key.
REL Software
release
Read in REPORT SLAVE ID (read-only)
Indirizzo Modbus
read input register 13
resolution and unit of measure
1
range
0 to 255
default
--
Non-modifi able parameter used to identify the software version installed
on the controller. The least signifi cant digit is used to identify functional
variations that do not imply changes to the parameter structure.
Parameters can only be copied between FCR controllers using the
programming key if the corresponding REL parameters are identical or
only the least signifi cant digit is diff erent (for example: copying is possible
between controllers with REL 12 and 14, while it is not possible between
controllers with REL 12 and 20). HW Even in INPUT REGISTER 14
HW
Hardware release
Read hardware version (read-only)
Indirizzo Modbus
read input register 14
resolution and unit of measure
1
range
0 to 255
default
--
Non-modifi able parameter used to identify the hardware version
TV/TI
Hardware release
Read hardware model (read-only)
Indirizzo Modbus
read input register 15 e 16
resolution and unit of measure
1
range
TV 23/40 – TI
06/09/12/20/40
default
--
Non-modifi able parameter used to identify the operating voltage and
current
WE Write
enable
Modbus address
read/write coil
1
resolution
and unit of measure
1
range
0/1
default
0
Parameter used to enable overriding of the output, and consequently
changes to variable EOVR
•
WE=0 override disabled
•
WE=1 override
enabled
HZMEM
Select frequency by internal parameter
Modbus address
read/write coil
2
resolution
and unit of measure
1
range
0/1
default
0
This parameter is used to select the operating frequency of the FCR
controller
•
HZMEM=0
50 Hz
•
HZMEM=1 60
HZ
LINMEM
Select operating curve
Modbus address
read/write coil
3
resolution
and unit of measure
1
range
0/1
default
0
This parameter is used to select linear or quadratic control
•
LINMEM=0 linear
•
LINMEM=1 quadratic
MINCUTMEM
Select minimum/cut-off mode
Modbus address
read/write coil
4
resolution
and unit of measure
1
range
0/1
default
1
This parameter is used to select how the controller responds to no control
signal (when INFCR = 0 or INMEM = 0)
•
MINCUTMEM=0 minimum
•
MINCUTMEM=1 cut-off
BAUD1MEM /
BAUD2MEM
Select baud rate
Modbus address
read/write coil
5 and 6
resolution
and unit of measure
1
range
0/1
default
1 & 0
Parameter used to select the serial line baud rate
Value
BAUD1MEM
BAUD2MEM
9600
0
0
19.200
1
0
38400
0
1
FDEF
Reset default
Modbus address
read/write coil
7
resolution
and unit of measure
1
range
0/1
default
0
Parameter used to reset the default values
•
FDEF=0
no action
•
FDEF=1
load default parameters
(also saved) – one-time action
SAVE
Save to memory
Modbus address
read/write coil
8
resolution
and unit of measure
1
range
0/1
default
0
Parameter used to save the parameter values to the internal memory
•
SAVE=0
no action
•
SAVE=1 save the parameters to the internal EEPROM:
one-time
action
IOVR
Override input
Modbus address
read/write coil
9
resolution
and unit of measure
1
range
0/1
default
0
Parameter used to override the input using a value set in the memory
(INMEM)
•
IOVR=0
no override
•
IOVR=1 enable
override