“FCR3 three-phase controller” +030222150 - rel. 1.3 - 12.01.2021
MODID
Digital input mode
Modbus address
read/write coil
10
resolution
and unit of measure
1
range
0/1
default
0
Parameter, to determine the digital input logic, used to activate the alarm
when the digital input status (STID) represents the reverse situation
•
MODID=0 normally closed input logic
•
MODID=1 normally open input logic
EOVR
Override output
Modbus address
read/write (*) coil
11
resolution
and unit of measure
1
range
0/1
default
0
Parameter to overwrite the output using a value set in the memory
(OUTMEM)
•
EOVR=0 no override
•
EOVR=1 enable
override
(*) Possibility to activeted the override only if parameter WE=1
SEL
Select controller settings
Modbus address
read discrete input
1 – Reading of Dip
S2.1
resolution
and unit of measure
1
range
0/1
default
R
Selects which parameters are used to manage operation of the controller.
Manual from FCR panel, Internal from FCR memory
•
SEL=0
Select manual from FCR panel (MAN) –
Use the variables with suffi
x FCR
•
SEL=1
Select internal from FCR memory (MEM)
Use the variables with suffi
x MEM
HZFCR
Select frequency from manual
Modbus address
read discrete input
2 – Reading of Dip
S2.4
resolution
and unit of measure
1
range
0/1
default
R
This parameter is used to select the operating frequency of the FCR
controller
•
HZFCR=0 50
Hz
•
HZFCR=1 60
HZ
LINFCR
Select operating curve
Modbus address
read discrete input
3 – Reading of Dip
S2.5
resolution
and unit of measure
1
range
0/1
default
R
This parameter is used to select linear or quadratic control
•
LINFCR=0 linear
•
LINFCR=1 quadratic
MINCUTFCR
Select minimum/cut-off mode
Modbus address
read discrete input
4 – Reading of Dip
S2.6
resolution
and unit of measure
1
range
0/1
default
R
This parameter is used to select how the controller responds to no control
signal (when INFCR = 0 or INMEM = 0).
•
MINCUTFCR=0 minimum
•
MINCUTFCR=1 cut-off
BAUD1FCR /
BAUD2FCR
Select baud rate
Modbus address
read discrete input
5/6 – Reading of
Dip S2.7 /8
resolution
and unit of measure
1
range
0/1
default
R
Parameter used to select the serial line baud rate
Value
BAUD1FCR
BAUD2FCR
9600
0
0
19.200
1
0
38400
0
1
ALRTMP
Temperature alarm status
Modbus address
read discrete input 7
resolution
and unit of measure
1
range
0/1
default
R
Indicates activation of the temperature alarm based on the reading of the
sensor on the FCR and the set thresholds
•
ALRTMP= 0
alarm deactivated
red LED does not change
•
ALRTMP= 1
alarm deactivated
red LED fl ashes
ALRPRC
Probe short-circuited alarm
Modbus address
read discrete input 8
resolution
and unit of measure
1
range
0/1
default
R
This alarm indicates whether the temperature sensor is short-circuited.
When this alarm is activated, temperature alarm is activeatd in the same
time.
•
ALRPRC= 0
alarm
deactivated
•
ALRPRC= 1
active alarm
sensor short-circuited
ALRPRO
Probe open alarm
Modbus address
read discrete input 9
resolution
and unit of measure
1
range
0/1
default
R
Indicates the temperature alarm disconected.
•
ALRPRO= 0
alarm
deactivated
•
ALRPRO= 1
active alarm, sensor disconnected.
STID
Status of inputs SW1 and SW2
Modbus address
read discrete input 10
resolution
and unit of measure
1
range
0/1
default
R
Indicates digital inputs SW1+SW2 state.
•
STID=0
inputs open
•
STID=0 inputs
closed
ALRM
Digital input alarm status
Modbus address
read discrete input 11
resolution
and unit of measure
1
range
0/1
default
R
Indicates activation of the alarm from digital inputs SW1 and SW2
•
ALRM=0 alarm not active
•
ALRM=1 alarm
active
FCRON
FCR status
Modbus address
read discrete input 12
resolution
and unit of measure
1
range
0/1
default
R
Indicates the status of the FCR controller
•
FCRON=0 controller off
•
FCRON=1 controller on