20
ENG
“EVD ice” +0300038EN - rel. 1.1 - 23.04.2018
a. on the “Rapid configuration” page, set parameters “p_GAS_TYPE” =
refrigerant and “p_SUPER_MAIN_REGULATION”= type of control;
Fig. 8.i
b. on the “Configuration” page, set parameter “p_SH_SET”.
Fig. 8.j
3.
Check whether there are other parameters that need to be set (see the
“Functions” chapter);
4.
Finally, select “Write” to copy the parameters to the controller.
Fig. 8.k
8.6 Setup using configuration file
On the Home page select “Device model”.
Fig. 8.l
The setup procedure comprises three steps:
1.
Create the configuration file;
2.
Copy the configuration file to the controller;
3.
Read the configuration file on the controller.
Create the configuration file
1.
Select the “Device setup” page;
2.
Set the parameters by double clicking, as shown in the figure:
a. on the “Rapid configuration” page, parameters “p_GAS_TYPE” =
refrigerant and “p_SUPER_MAIN_REGULATION”= type of control;
b. on the “Configuration” page, parameter “p_SH_SET”.
Fig. 8.m
3.
Save the list of parameters with a new name, for example “NEW_NAME.
hex”. To load and display a list saved by the user, select “Load” and
navigate to the path where the file is saved. On the other hand,
to load a list of parameters supplied by CAREL, select “Load” and
navigate the following path:
Load
à
Plugins
à
Commissioning EVD mini
à
TXT
à
TXT32.
Save
Load
Copy the configuration file to the controller
Select “Update device” and:
a. Click button (A) to open the drop-down menu;
NEW_NAME.hex
C
B
A
Fig. 8.n
b. Select the list of parameters corresponding to the project file
created:
“NEW_NAME.hex”;
c. Click “Update” to UPLOAD the parameters to the controller.
8.7 Read the configuration file on the
controller
1.
Go to the “Home” page and select RS485 (rear connector);
2.
Go to “Device setup” to read the list of parameters on the controller and
make sure the settings are correct.