Carel EVD ice Скачать руководство пользователя страница 13

13

ENG

“EVD ice” +0300038EN - rel. 1.1 - 23.04.2018

5.  FUNCTIONS

A low superheat temperature in fact corresponds to a situation of probable 
instability due to the turbulent evaporation process approaching the 
measurement point of the probes. The expansion valve must therefore 
be controlled with extreme precision and a reaction capacity around 
the superheat set point, which will almost always vary from 3 to 14 K. 
Set point values outside of this range are quite infrequent and relate to 
special applications.

P

E

V

S

F

L

M

T

CP

C

EEV

S1

S2

Fig. 5.a

Key

CP compressor

EEV electronic expansion valve

C

condenser

V

solenoid valve

L

liquid receiver

E

evaporator

F

dewatering filter

P

pressure probe (transducer)

S

liquid indicator

T

temperature probe

For the wiring, see 

“Wiring description”.

5.1  Control

EVD ice is a superheat controller. The type of refrigeration unit can be 
selected using the “Operating mode” parameter.

Parameter/description

Def.

Operating mode 

1 Multiplexed cabinet/cold room

2 Air-conditioner/chiller with plate heat exchanger

3 Air-conditioner/chiller with tube bundle heat exchanger

4 Air-conditioner/chiller with finned coil heat exchanger

5 Reserved

6 Reserved

7 Banco frigo/cella con CO2 (R744) sub-critica

1 = multiple-
xed cabinet/
cold room

Tab. 5.a

Based on the operating mode setting , the driver automatically sets a 
series of control parameters.

Operating mode

PID: pro-

port. gain

PID: integra-

tion time

Superheat 

set point

LowSH protection

LOP protection 

MOP protection

threshold Integra-

tion time

threshold Integra-

tion time

thre-

shold

Integra-

tion time

1 Multiplexed cabinet/cold room

15

150

11

5

15

-50

0

50

20

2 Air-conditioner/chiller with plate heat exchanger

3

40

6

2

2,5

-50

4

50

10

3 Air-conditioner/chiller with tube bundle heat exchanger  

5

60

6

2

2,5

-50

4

50

10

4 Air-conditioner/chiller with finned coil heat exchanger

10

100

6

2

10

-50

10

50

20

5 Reserved

-

-

-

-

-

-

-

-

-

6 Reserved

-

-

-

-

-

-

-

-

-

7 Banco frigo/cella con CO2 (R744) sub-critica

20

400

13

7

15

-50

0

50

20

Tab. 5.b 

Superheat

The primary purpose of the electronic valve is ensure that the flow-rate 
of refrigerant that flows through the nozzle corresponds to the flow-rate 
required by the compressor. In this way, the evaporation process will take 
place along the entire length of the evaporator and there will be no liquid 
at the outlet (consequently in the branch that runs to the compressor). As 
liquid is not compressible, it may cause damage to the compressor and even 
breakage if the quantity is considerable and the situation lasts some time.

Superheat control

The parameter that the control of the electronic valve is based on is 
the superheat temperature, which effectively tells whether or not there 
is liquid at the end of the evaporator. The superheat temperature is 
calculated as the difference between: superheated gas temperature 
(measured by a temperature probe located at the end of the evaporator) 
and the saturated evaporation temperature (calculated based on the 
reading of a pressure transducer located at the end of the evaporator and 
using the Tsat(P) conversion curve for each refrigerant).

Superheat

=

Superheated gas 

temperature 

(*)

Saturated evaporation 

temperature

(*) suction

If the superheat temperature is high it means that the evaporation 
process is completed well before the end of the evaporator, and therefore 
flow-rate of refrigerant through the valve is insufficient. This causes a 
reduction in cooling efficiency due to the failure to exploit part of the 
evaporator. The valve must therefore be opened further. Vice-versa, if 
the superheat temperature is low it means that the evaporation process 
has not concluded at the end of the evaporator and a certain quantity 
of liquid will still be present at the inlet to the compressor. The valve 
must therefore be closed further. The operating range of the superheat 
temperature is limited at the lower end: if the flow-rate through the valve 
is excessive the superheat measured will be near 0 K. This indicates the 
presence of liquid, even if the percentage of this relative to the gas cannot 
be quantified. There is therefore un undetermined risk to the compressor 
that must be avoided. Moreover, a high superheat temperature as 
mentioned corresponds to an insufficient flow-rate of refrigerant. The 
superheat temperature must therefore always be greater than 0 K and 
have a minimum stable value allowed by the valve-unit system. 

Содержание EVD ice

Страница 1: ...H i g h E f f i c i e n c y S o l u t i o n s EVD ice NO POWER SIGNAL CABLES TOGETHER READ CAREFULLY IN THE TEXT User manual Superheat control for unipolar electronic expansion valve...

Страница 2: ......

Страница 3: ...not use corrosive chemicals solvents or aggressive detergents to clean the device do not use the product for applications other than those specified in the technical manual All of the above suggestio...

Страница 4: ......

Страница 5: ...2 Special control function smooth lines 14 5 3 Service parameters 14 6 PROTECTORS 15 6 1 Protectors 15 7 PARAMETERS TABLE 17 8 NETWORK CONNECTION 18 8 1 RS485 serial configuration 18 8 2 Network conne...

Страница 6: ......

Страница 7: ...om controllers 1 1 Models P N Description EVDM011R3 EVD ice 115 230 V E2V stator display EVDM011R1 EVD ice 115 230 V E2V stator display Ultracap module connector EVDM011R4 EVD ice 115 230 V E3V stator...

Страница 8: ...portant install EVD ice on the evaporator away from the places where ice forms connect the power and serial cables in the IP65 junction box for assembly of the E2V E3V valve see the ExV system guide 0...

Страница 9: ...Regulator P T EEV M Condenser Electrical panel Compressor Condenser unit Evaporator unit Solenoid valve IP65 L N Fig 2 d WITHOUT SOLENOID VALVE WITH ULTRACAP MODULE COLD ROOM IN COLD ROOM OUT COLD RO...

Страница 10: ...d pressure probe see the chapter on Commissioning 2 connectthepowercableandthedigitalinputcable forthemaximum length see the technical specifications 3 poweronthedriver thedisplaywilllightup andthedri...

Страница 11: ...than 9 are displayed in two steps first the sign then the tens and units GASType Mode Super Heat GASType Mode Super Heat 123 GASType Mode Super Heat GASType Mode Super Heat 99 Fig 3 b Note the decima...

Страница 12: ...Superheat set point GASType Mode Super Heat 7 Press PRG Set for 2 seconds to exit the commissioning procedure and start control The standard display is shown 4 2 Parameters first configuration Import...

Страница 13: ...through the nozzle corresponds to the flow rate required by the compressor In this way the evaporation process will take place along the entire length of the evaporator and there will be no liquid at...

Страница 14: ...ol temperature approaches the set point the Smooth_line parameter is used to prevent the valve from closing by reducing the evaporator s cooling capacity In order to use this function the digital inpu...

Страница 15: ...activation threshold depending on the operating conditions of the controlled unit this is set in Service programming mode integration time which determines the intensity if set to 0 the protector is...

Страница 16: ...refrigerant charge or when there are sudden variations in the load The protector is also useful in multiplexed systems showcases as allows all the utilities to be enabled at the same time without cau...

Страница 17: ...Po Valve opening 0 100 A 1 0 R CP PID proportional gain 15 0 800 A 11 10 R W ti PID integral time 150 0 999 s I 17 144 R W C1 LowSH protection threshold 5 9 5 9 Superheat set point K F A 12 11 R W C2...

Страница 18: ...00 2 stop bit parity odd 15 4800 1 stop bit parity odd 16 9600 1 stop bit parity odd 17 19200 1 stop bit parity odd 2 0 17 Important all controllers connected in a serial network need to be set with t...

Страница 19: ...RS485 rear connector Offline Device model Online Offline Device setup Read instant values of control parameters Select Load to load a list of project parameters hex modify and save a new project Setup...

Страница 20: ...iguration page parameters p_GAS_TYPE refrigerant and p_SUPER_MAIN_REGULATION type of control b on the Configuration page parameter p_SH_SET Fig 8 m 3 Savethelistofparameterswithanewname forexample NEW...

Страница 21: ...om dew_f_l Dew f low 17239 32768 32767 I 35 162 R W Net_alarm Network alarm 0 0 1 D 1 0 R all E6 Emergency_closing_alarm Mains power failure 0 0 1 D 2 1 R all E5 S1_alarm Probe S1 alarm 0 0 1 D 3 2 R...

Страница 22: ...r or when reaching the control set point It can also occur when opening the digital input which involves closing the valve or in the event of a probe alarm In general it can be said that the electroni...

Страница 23: ...a power failure proceed as follows remove the valve stator set the PID proportional gain 0 The valve will remain stopped at the initial opening position set by corresponding parameter Retrieve physica...

Страница 24: ...ent of probe or valve malfunctions to protect the compressor using the relay to control the solenoid valve or to simply signal a possible risk In fact incorrect measurement of the evaporation pressure...

Страница 25: ...inets only Decrease the value of the Valve opening at start up parameter on all the utilities making sure that there are no repercussions on the control temperature Liquid returns to the compressor on...

Страница 26: ...the valve by placing it in manual control and closing or opening it com pletely One complete opening must bring a decrease in the superheat and vice versa If the movement is reversed check the electri...

Страница 27: ......

Страница 28: ...EL INDUSTRIES HeadQuarters Via dell Industria 11 35020 Brugine Padova Italy Tel 39 049 9716611 Fax 39 049 9716600 e mail carel carel com www carel com Agenzia Agency EVD ice 0300038EN rel 1 1 23 04 20...

Отзывы: