Carel EVD ice Скачать руководство пользователя страница 15

15

ENG

“EVD ice” +0300038EN - rel. 1.1 - 23.04.2018

Example 1:

 The pressure read is 20 barg this will be immediately 

converted to the corresponding value of 290 psig.

Example 2:

 The “superheat set point” parameter set to 10 K will be 

immediately converted to the corresponding value of 18 °F.

Access to the Mode (operating mode) parameter (par. IA)

To avoid accidental modification of the controller’s operating mode, it is 
possible to disable the access to the corresponding parameter.

Par. Description

Def. Min. Max. UoM

IA

Enable operating mode modification
0/1 = yes/ no

0

0

1

-

Number of control steps (par. U3)

Total number of steps between the valve fully closed and fully open 
position 

Par. Description

Def. Min. Max. UoM

U3 Number of valve control steps

1 / 2 = 480/960 steps

1

1

2

-

Digital input

The function of the digital input can be set by parameter:

Par. Description

Def. Min. Max. UoM

di

DI configuration
1=Start/Stop regulation
2=Regulation backup

1

1

2

-

Start/stop regulation:

• 

digital input closed: control active;

• 

digital input open: control in standby (see the paragraph “Control 
states”).

Important:

 this setting excludes activation/deactivation of control

via the network. See the following function.

Regulation  backup:

 if there is a network connection and communication 

fails, the driver checks the status of the digital input to determine whether 
control is active or in standby.

6.  PROTECTORS

These are additional functions that are activated in specific situations that 
are potentially dangerous for the unit being controlled. They feature an 
integral action, that is, the action increases gradually when moving away 
from the activation threshold. They may add to or overlap (disabling) 
normal PID superheat control. By separating the management of these 
functions from PID control, the parameters can be set separately, allowing, 
for example, normal control that is less reactive yet much faster in 
responding when exceeding the activation limits of one of the protectors.

6.1  Protectors

The protectors are 3:

• 

LowSH, low superheat;

• 

LOP, low evaporation temperature;

• 

MOP, high evaporation temperature;

The protectors have the following main features:

• 

activation threshold: depending on the operating conditions of the 
controlled unit, this is set in Service programming mode;

• 

integration time, which determines the intensity (if set to 0, the 
protector is disabled): set automatically based on the type of main 
control;

• 

alarm, with activation threshold (the same as the protector) and 
timeout (if set to 0 disables the alarm signal).

 

Note:  

The alarm signal is independent from the effectiveness of 

the protector, and only signals that the corresponding threshold has 
been exceeded. If a protector is disabled (null integration time), the 
relative alarm signal is also disabled.
Each protector is influenced by the proportional gain parameter (CP) of 
PID superheat control. The higher is the value of CP, the more intensely 
the protection will react.

Characteristics of the protectors

Protection

Reaction

Reset

LowSH

Intense closing

Immediate

LOP

Intense opening

Immediate

MOP

Moderate closing

Controlled

Tab. 6.a

Reaction:

 summary description of the type of action in controlling the 

valve.

Reset:

 summary description of the type of reset following the activation 

of the protector. Reset is controlled to avoid swings around the activation 
threshold or immediate reactivation of the protector.

 

Note:

 all alarms are generated after a fixed delay, as shown in the table:

Protectors

Delay (s)

LowSH

300

LOP

300

MOP

600

LowSH (low superheat)

The protector is activated so as to prevent the low superheat from 
causing the return of liquid to the compressor.

Par. Description

Def. Min. Max.

U.M.

C1 LowSH protection: threshold

5(9) -5(-9) Set point 

superheat

K(°F)

C2 LowSH protection: integration time

15

0

800

s

When the superheat value falls below the threshold, the system enters low 
superheat status, and the intensity with which the valve is closed is increased: 
the more the superheat falls below the threshold, the more intensely the 
valve will close. The LowSH threshold must be less than or equal to the 
superheat set point. The low superheat integration time indicates the 
intensity of the action: the lower the value, the more intense the action. 

The integration time is set automatically based on the type of main 

control.

t

t

t

OFF

ON

A

OFF

ON

Low_SH

Low_SH_TH

SH

D

B

Fig. 6.a

key:

SH

Superheat

A

Alarm

Low_SH_TH Low_SH protection threshold

D

Alarm delay

Low_SH

Low_SH protection

t

Time

B

Alarm automatic reset

Содержание EVD ice

Страница 1: ...H i g h E f f i c i e n c y S o l u t i o n s EVD ice NO POWER SIGNAL CABLES TOGETHER READ CAREFULLY IN THE TEXT User manual Superheat control for unipolar electronic expansion valve...

Страница 2: ......

Страница 3: ...not use corrosive chemicals solvents or aggressive detergents to clean the device do not use the product for applications other than those specified in the technical manual All of the above suggestio...

Страница 4: ......

Страница 5: ...2 Special control function smooth lines 14 5 3 Service parameters 14 6 PROTECTORS 15 6 1 Protectors 15 7 PARAMETERS TABLE 17 8 NETWORK CONNECTION 18 8 1 RS485 serial configuration 18 8 2 Network conne...

Страница 6: ......

Страница 7: ...om controllers 1 1 Models P N Description EVDM011R3 EVD ice 115 230 V E2V stator display EVDM011R1 EVD ice 115 230 V E2V stator display Ultracap module connector EVDM011R4 EVD ice 115 230 V E3V stator...

Страница 8: ...portant install EVD ice on the evaporator away from the places where ice forms connect the power and serial cables in the IP65 junction box for assembly of the E2V E3V valve see the ExV system guide 0...

Страница 9: ...Regulator P T EEV M Condenser Electrical panel Compressor Condenser unit Evaporator unit Solenoid valve IP65 L N Fig 2 d WITHOUT SOLENOID VALVE WITH ULTRACAP MODULE COLD ROOM IN COLD ROOM OUT COLD RO...

Страница 10: ...d pressure probe see the chapter on Commissioning 2 connectthepowercableandthedigitalinputcable forthemaximum length see the technical specifications 3 poweronthedriver thedisplaywilllightup andthedri...

Страница 11: ...than 9 are displayed in two steps first the sign then the tens and units GASType Mode Super Heat GASType Mode Super Heat 123 GASType Mode Super Heat GASType Mode Super Heat 99 Fig 3 b Note the decima...

Страница 12: ...Superheat set point GASType Mode Super Heat 7 Press PRG Set for 2 seconds to exit the commissioning procedure and start control The standard display is shown 4 2 Parameters first configuration Import...

Страница 13: ...through the nozzle corresponds to the flow rate required by the compressor In this way the evaporation process will take place along the entire length of the evaporator and there will be no liquid at...

Страница 14: ...ol temperature approaches the set point the Smooth_line parameter is used to prevent the valve from closing by reducing the evaporator s cooling capacity In order to use this function the digital inpu...

Страница 15: ...activation threshold depending on the operating conditions of the controlled unit this is set in Service programming mode integration time which determines the intensity if set to 0 the protector is...

Страница 16: ...refrigerant charge or when there are sudden variations in the load The protector is also useful in multiplexed systems showcases as allows all the utilities to be enabled at the same time without cau...

Страница 17: ...Po Valve opening 0 100 A 1 0 R CP PID proportional gain 15 0 800 A 11 10 R W ti PID integral time 150 0 999 s I 17 144 R W C1 LowSH protection threshold 5 9 5 9 Superheat set point K F A 12 11 R W C2...

Страница 18: ...00 2 stop bit parity odd 15 4800 1 stop bit parity odd 16 9600 1 stop bit parity odd 17 19200 1 stop bit parity odd 2 0 17 Important all controllers connected in a serial network need to be set with t...

Страница 19: ...RS485 rear connector Offline Device model Online Offline Device setup Read instant values of control parameters Select Load to load a list of project parameters hex modify and save a new project Setup...

Страница 20: ...iguration page parameters p_GAS_TYPE refrigerant and p_SUPER_MAIN_REGULATION type of control b on the Configuration page parameter p_SH_SET Fig 8 m 3 Savethelistofparameterswithanewname forexample NEW...

Страница 21: ...om dew_f_l Dew f low 17239 32768 32767 I 35 162 R W Net_alarm Network alarm 0 0 1 D 1 0 R all E6 Emergency_closing_alarm Mains power failure 0 0 1 D 2 1 R all E5 S1_alarm Probe S1 alarm 0 0 1 D 3 2 R...

Страница 22: ...r or when reaching the control set point It can also occur when opening the digital input which involves closing the valve or in the event of a probe alarm In general it can be said that the electroni...

Страница 23: ...a power failure proceed as follows remove the valve stator set the PID proportional gain 0 The valve will remain stopped at the initial opening position set by corresponding parameter Retrieve physica...

Страница 24: ...ent of probe or valve malfunctions to protect the compressor using the relay to control the solenoid valve or to simply signal a possible risk In fact incorrect measurement of the evaporation pressure...

Страница 25: ...inets only Decrease the value of the Valve opening at start up parameter on all the utilities making sure that there are no repercussions on the control temperature Liquid returns to the compressor on...

Страница 26: ...the valve by placing it in manual control and closing or opening it com pletely One complete opening must bring a decrease in the superheat and vice versa If the movement is reversed check the electri...