“EVD ice” +0300038EN - rel. 1.1 - 23.04.2018
7. PARAMETERS TABLE
Par.
Description
Def.
Min.
Max.
UoM
Type Carel Modbus® R/W Note
BASED (FISRT CONFIGURATION)
GAS
Type
Refrigerant
3
0
40
-
I
12
139
R/W
Gas Type =
Refrigerant
0
Custom
1 R22
15 R422D
28 R1234ze(-1...4.2 barg)
2 R134a
16 R413A
29 R455A (-1...12.8 barg)
3 R404A
17 R422A
30 R170 (0...17.3 barg)
4 R407C
18 R423A
31 R442A (-1...12.8 barg)
5 R410A
19 R407A
32 R447A (-1...12.8 barg)
6 R507A
20 R427A
33 R448A
7 R290
21 R245FA
34 R449A
8 R600 (-1...4.2 barg)
22 R407F
35 R450A (-1...4.2 barg)
9 R600a (-1...4.2 barg) 23 R32 (0...17.3 barg) 36 R452A (-1...12.8 barg)
10 R717
24 HTR01
37 R508B (-1...4.2 barg)
11 R744 (0...45 barg)
25 HTR02
38 R452B
12 R728
26 R23
39 R513A (-1...4.2 barg)
13 R1270
27 R1234yf
40 R454B
14 R417A
41 R458A
3 = R404A
Mode Operating mode
1 Multiplexed cabinet/cold room
2 Air-conditioner/chiller with plate heat exchanger
3 Air-conditioner/chiller with tube bundle heat exchanger
4 Air-conditioner/chiller with finned coil heat exchanger
5 Reserved
6 Reserved
7 Cabinet/cold room with subcritical (R744) CO2
1
1
7
-
I
13
140
R/W
Super
Heat
Superheat set point
11
(20)
LowSH:
protection
threshold
55
(99)
K
(°F)
A
10
9
R/W
SERVICE
P1
S1 probe measurement
-
-85
(-290)
200
(2900)
barg (psig)
A
6
5
R
P2
S2 probe measurement
-
-85
(-121)
200
(392)
°C(°F)
A
7
6
R
tE
Evaporation temperature (converted)
-
-85 (-121)
200 (392)
°C(°F)
A
4
3
R
tS
Suction temperature
-
-85 (-121)
200 (392)
°C(°F)
A
3
2
R
Po
Valve opening
-
0
100
%
A
1
0
R
CP
PID proportional gain
15
0
800
-
A
11
10
R/W
ti
PID integral time
150
0
999
s
I
17
144
R/W
C1
LowSH protection: threshold
5(9)
-5
(-9)
Superheat
set point
K
(°F)
A
12
11
R/W
C2
LowSH protection: integral time
15
0
800
s
A
13
12
R/W
C3
LOP protection: threshold
-50(-
58)
-85(-121)
MOP
protection
threshold
°C(°F)
A
14
13
R/W
C4
LOP protection: integral time
0
0
800
s
A
15
14
R/W
C5
MOP protection: threshold
50
(122)
LOP pro-
tection:
threshold
200
(392)
°C(°F)
A
16
15
R/W
C6
MOP protection: integral time
20
0
800
s
A
17
16
R/W
C7
MOP protection: disabling threshold
30
(86)
-85
(-121)
200
(392)
°C(°F)
A
19
18
R/W
C8
Low suction temperature alarm threshold
-50
(-58)
-85
(-121)
200
(392)
°C(°F)
A
18
17
R/W
S1
S1 probe type
Ratiometric (OUT=0…5V)
1 = -1…4.2 barg
8 = -1…12.8 barg
2 = 0.4…9.3 barg
9 = 0…20.7 barg
3 = -1…9.3 barg
10 = 1.86…43.0 barg
4 = 0…17.3 barg
11 = Reserved
5 = 0.85…34.2 barg
12 = 0…60 barg
6 = 0…34.5 barg
13 = 0…90 barg
7 = 0…45 barg
3
1
11
-
I
14
141
R/W
n1
Network address
99
1
99
-
I
10
137
R/W
n2
Baud rate (bit/s)
0 4800, 2 stop bit, parity none
9
4800, 1 stop bit, parity even
1
9600, 2 stop bit, parity none
10 9600, 1 stop bit, parity even
2
19200, 2 stop bit, parity none 11 19200, 1 stop bit, parity even
3
4800, 1 stop bit, parity none
12 4800, 2 stop bit, parity odd
4
9600, 1 stop bit, parity none
13 9600, 2 stop bit, parity odd
5
19200, 1 stop bit, parity none 14 19200, 2 stop bit, parity odd
6
4800, 2 stop bit, parity even
15 4800, 1 stop bit, parity odd
7
9600, 2 stop bit, parity even
16 9600, 1 stop bit, parity odd
8
19200, 2 stop bit, parity even
17 19200, 1 stop bit, parity odd
2
0
17
-
I
20
147
R/W