Carel EVD ice Скачать руководство пользователя страница 12

12

ENG

“EVD ice” +0300038EN - rel. 1.1 - 23.04.2018

4.  COMMISSIONING

Important:

 if the refrigerant is not available among the refrigerant 

parameter options, contact CAREL service to:

1. 

confirm that the system: (c.pCO/Ultracella,...)+ EVD ice + CAREL electronic 
expansion valve is compatible with the desired refrigerant (Gas 
type=custom);

2. 

identify the values that define the custom refrigerant and enter them for 
parameters: “Dew a…f high/low” . See the variables accessible via 
serial connection.

4.1  Commissioning procedure

Once the electrical connections have been completed (see the chapter 
“Installation”) and the power supply has been connected, the operations 
required for commissioning the driver depend on the type of interface 
used, however essentially involve setting just 3 parameters: refrigerant,  
functioning mode

, superheat setpoint.

Important:

• 

until the commissioning procedure has been completed, control 
will not be active;

• 

(only during commissioning) changing the gas involves changing 
the value of the ratiometric probe parameter.

After powering up the driver, the display lights and the driver waits the 
control parameters, indicated by the hyphens. The default parameters 
are:

1. 

Refrigerant = R404A;

2. 

Type of control  = multiplexed showcase/cold room

3. 

Superheat set point  = 11 K.

Procedure:

GAS Type

Mode

Super Heat

1. 

The controller displays the bar at the top: refrigerant (GAS Type); 

GAS Type

Mode

Super Heat

2. 

Press PRG/Set: the refrigerant setting is shown = 3: R404A

GAS Type

Mode

Super Heat

3. 

Press UP/Down to change the value

GAS Type

Mode

Super Heat

4. 

Press PRG/Set to save and return to the refrigerant parameter code 
(bar at the top)

GAS Type

Mode

Super Heat

5. 

Press Down to move to the next parameter: Mode, indicated by the 
bar in the middle;

6. 

Repeat steps 2,3,4,5, to set the values of the other parameters: Mode, 
Superheat set point;

GAS Type

Mode

Super Heat

7. 

Press PRG/Set for 2 seconds to exit the commissioning procedure 
and start control. The standard display is shown.

4.2  Parameters first configuration

Important:

 ONLY DURING commissioning, changing the gas 

involves changing the value of the ratiometric probe parameter; if not 
specified in the table, the type of ratiometric probe is -1...9.3 barg.

Parameter/ description

Def.

Gas Type = refrigerant

0 Custom

1 R22

15 R422D

28 R1234ze(-1...4.2 barg)

2 R134a

16 R413A

29 R455A (-1...12.8 barg)

3 R404A

17 R422A

30 R170 (0...17.3 barg)

4 R407C

18 R423A

31 R442A (-1...12.8 barg)

5 R410A

19 R407A

32 R447A (-1...12.8 barg)

6 R507A

20 R427A

33 R448A

7 R290

21 R245FA

34 R449A

8 R600(-1...4.2 barg)

22 R407F

35 R450A (-1...4.2 barg)

9 R600a (-1...4.2 barg) 23 R32 (0...17.3 barg) 36 R452A (-1...12.8 barg)

10 R717

24 HTR01

37 R508B (-1...4.2 barg)

11 R744 (0...45 barg)

25 HTR02

38 R452B

12 R728

26 R23

39 R513A (-1...4.2 barg)

13 R1270

27 R1234yf

40 R454B

14 R417A

41 R458A

3 = 
R404A

Tab. 4.a

Note:

 

if the refrigerant is not available among the refrigerant 

options, “GAS Type=refrigerant”:
1. 

set any refrigerant (for example R404);

2. 

select the type of operating mode (Mode), the superheat set point 
and complete the commissioning procedure;

3. 

use the VPM program (Visual Parameter Manager, see the chapter 
“Network connection” ) and set the refrigerant type “0= Custom” and 
the parameters “Dew a...f high/low” which define the refrigerant (see 
variables accessible via serial connection);

4. 

start control, for example by closing the digital input contact to 
enable operation. 

Mode = operating mode

1 Multiplexed cabinet/cold room

2 Air-conditioner/chiller with plate heat exchanger

3 Air-conditioner/chiller with tube bundle heat exchanger

4 Air-conditioner/chiller with finned coil heat exchanger

5 Reserved

6 Reserved

7 Cabinet/cold room with subcritical (R744) CO2

1 = Mul-
tiplexed 
cabinet/
cold room

Superheat setpoint

11 K(20°F)

Tab. 4.b

Note:

 

consider the unit of measure (°C/°F) when setting the 

superheat setpoint (Si parameter).

Содержание EVD ice

Страница 1: ...H i g h E f f i c i e n c y S o l u t i o n s EVD ice NO POWER SIGNAL CABLES TOGETHER READ CAREFULLY IN THE TEXT User manual Superheat control for unipolar electronic expansion valve...

Страница 2: ......

Страница 3: ...not use corrosive chemicals solvents or aggressive detergents to clean the device do not use the product for applications other than those specified in the technical manual All of the above suggestio...

Страница 4: ......

Страница 5: ...2 Special control function smooth lines 14 5 3 Service parameters 14 6 PROTECTORS 15 6 1 Protectors 15 7 PARAMETERS TABLE 17 8 NETWORK CONNECTION 18 8 1 RS485 serial configuration 18 8 2 Network conne...

Страница 6: ......

Страница 7: ...om controllers 1 1 Models P N Description EVDM011R3 EVD ice 115 230 V E2V stator display EVDM011R1 EVD ice 115 230 V E2V stator display Ultracap module connector EVDM011R4 EVD ice 115 230 V E3V stator...

Страница 8: ...portant install EVD ice on the evaporator away from the places where ice forms connect the power and serial cables in the IP65 junction box for assembly of the E2V E3V valve see the ExV system guide 0...

Страница 9: ...Regulator P T EEV M Condenser Electrical panel Compressor Condenser unit Evaporator unit Solenoid valve IP65 L N Fig 2 d WITHOUT SOLENOID VALVE WITH ULTRACAP MODULE COLD ROOM IN COLD ROOM OUT COLD RO...

Страница 10: ...d pressure probe see the chapter on Commissioning 2 connectthepowercableandthedigitalinputcable forthemaximum length see the technical specifications 3 poweronthedriver thedisplaywilllightup andthedri...

Страница 11: ...than 9 are displayed in two steps first the sign then the tens and units GASType Mode Super Heat GASType Mode Super Heat 123 GASType Mode Super Heat GASType Mode Super Heat 99 Fig 3 b Note the decima...

Страница 12: ...Superheat set point GASType Mode Super Heat 7 Press PRG Set for 2 seconds to exit the commissioning procedure and start control The standard display is shown 4 2 Parameters first configuration Import...

Страница 13: ...through the nozzle corresponds to the flow rate required by the compressor In this way the evaporation process will take place along the entire length of the evaporator and there will be no liquid at...

Страница 14: ...ol temperature approaches the set point the Smooth_line parameter is used to prevent the valve from closing by reducing the evaporator s cooling capacity In order to use this function the digital inpu...

Страница 15: ...activation threshold depending on the operating conditions of the controlled unit this is set in Service programming mode integration time which determines the intensity if set to 0 the protector is...

Страница 16: ...refrigerant charge or when there are sudden variations in the load The protector is also useful in multiplexed systems showcases as allows all the utilities to be enabled at the same time without cau...

Страница 17: ...Po Valve opening 0 100 A 1 0 R CP PID proportional gain 15 0 800 A 11 10 R W ti PID integral time 150 0 999 s I 17 144 R W C1 LowSH protection threshold 5 9 5 9 Superheat set point K F A 12 11 R W C2...

Страница 18: ...00 2 stop bit parity odd 15 4800 1 stop bit parity odd 16 9600 1 stop bit parity odd 17 19200 1 stop bit parity odd 2 0 17 Important all controllers connected in a serial network need to be set with t...

Страница 19: ...RS485 rear connector Offline Device model Online Offline Device setup Read instant values of control parameters Select Load to load a list of project parameters hex modify and save a new project Setup...

Страница 20: ...iguration page parameters p_GAS_TYPE refrigerant and p_SUPER_MAIN_REGULATION type of control b on the Configuration page parameter p_SH_SET Fig 8 m 3 Savethelistofparameterswithanewname forexample NEW...

Страница 21: ...om dew_f_l Dew f low 17239 32768 32767 I 35 162 R W Net_alarm Network alarm 0 0 1 D 1 0 R all E6 Emergency_closing_alarm Mains power failure 0 0 1 D 2 1 R all E5 S1_alarm Probe S1 alarm 0 0 1 D 3 2 R...

Страница 22: ...r or when reaching the control set point It can also occur when opening the digital input which involves closing the valve or in the event of a probe alarm In general it can be said that the electroni...

Страница 23: ...a power failure proceed as follows remove the valve stator set the PID proportional gain 0 The valve will remain stopped at the initial opening position set by corresponding parameter Retrieve physica...

Страница 24: ...ent of probe or valve malfunctions to protect the compressor using the relay to control the solenoid valve or to simply signal a possible risk In fact incorrect measurement of the evaporation pressure...

Страница 25: ...inets only Decrease the value of the Valve opening at start up parameter on all the utilities making sure that there are no repercussions on the control temperature Liquid returns to the compressor on...

Страница 26: ...the valve by placing it in manual control and closing or opening it com pletely One complete opening must bring a decrease in the superheat and vice versa If the movement is reversed check the electri...

Страница 27: ......

Страница 28: ...EL INDUSTRIES HeadQuarters Via dell Industria 11 35020 Brugine Padova Italy Tel 39 049 9716611 Fax 39 049 9716600 e mail carel carel com www carel com Agenzia Agency EVD ice 0300038EN rel 1 1 23 04 20...

Отзывы: