Carel EVD ice Скачать руководство пользователя страница 16

16

ENG

“EVD ice” +0300038EN - rel. 1.1 - 23.04.2018

LOP (low evaporation pressure)

LOP= Low Operating Pressure
The LOP protection threshold is applied as a saturated evaporation 
temperature value so that it can be easily compared against the technical 
specifications supplied by the manufacturers of the compressors. The 
protector is activated so as to prevent too low evaporation temperatures 
from stopping the compressor due to the activation of the low pressure 
switch. The protector is very useful in units with compressors on board 
(especially multi-stage), where when starting or increasing capacity the 
evaporation temperature tends to drop suddenly. When the evaporation 
temperature falls below the low evaporation temperature threshold, 
the system enters LOP status and is the intensity with which the valve is 
opened is increased. The further the temperature falls below the threshold, 
the more intensely the valve will open. The integration time indicates the 
intensity of the action: the lower the value, the more intense the action.

Par. Description

Def. Min. Max.

U.M.

C3 LOP protection: threshold

-50 
(-58)

-85 
(-121)

MOP protec.: 
threshold

C(°F)

C4 LOP protection: integration time

0

0

800

s

The integration time is set automatically based on the type of main 

control.

 Note: 

• 

the LOP threshold must be lower then the rated evaporation 
temperature of the unit, otherwise it would be activated unnecessarily, 
and greater than the calibration of the low pressure switch, otherwise 
it would be useless. As an initial approximation it can be set to a value 
exactly half-way between the two limits indicated;

• 

the protector has no purpose in multiplexed systems (showcases) 
where the evaporation is kept constant and the status of the individual 
electronic valve does not affect the pressure value;

• 

the LOP alarm can be used as an alarm to highlight refrigerant leaks by 
the circuit. A refrigerant leak in fact causes an abnormal lowering of the 
evaporation temperature that is proportional, in terms of speed and 
extent, to the amount of refrigerant dispersed. 

 

t

t

t

OFF

ON

ALARM

OFF

ON

LOP

LOP_TH

T_EVAP

D

B

Fig. 6.b

Key:

T_EVAP Evaporation temperature

D

Alarm timeout

LOP_TH Low evaporation temperature protection ALARM Alarm

LOP

LOP protection

t

Time

B

Automatic alarm reset

MOP (high evaporation pressure)

MOP= Maximum Operating Pressure.
The MOP protection threshold is applied as a saturated evaporation 
temperature value so that it can be easily compared against the technical 
specifications supplied by the manufacturers of the compressors. The 
protector is activated so as to prevent too high evaporation temperatures 
from causing an excessive workload for the compressor, with consequent 
overheating of the motor and possible activation of the thermal protector. 
The protector is very useful in self-contained units if starting with a high 
refrigerant charge or when there are sudden variations in the load. The 
protector is also useful in multiplexed systems (showcases), as allows all 
the utilities to be enabled at the same time without causing problems 
of high pressure for the compressors. To reduce the evaporation 
temperature, the output of the refrigeration unit needs to be decreased. 
This can be done by controlled closing of the electronic valve, implying 

superheat is no longer controlled, and an increase in the superheat 
temperature. The protector will thus have a moderate reaction that tends 
to limit the increase in the evaporation temperature, keeping it below the 
activation threshold while trying to stop the superheat from increasing 
as much as possible. Normal operating conditions will not resume based 
on the activation of the protector, but rather on the reduction in the 
refrigerant charge that caused the increase in temperature. The system 
will therefore remain in the best operating conditions (a little below the 
threshold) until the load conditions change.  

Par. Description

Def. Min.

Max. U.M.

C5 MOP protection threshold 

50 
(122)

Protection LOP: 
threshold

200
(392)

C(°F)

C6 MOP protection integration time 20

0

800 s

The integration time is set automatically based on the type of main 

control.

When the evaporation temperature rises above the MOP threshold, the 
system enters MOP status, superheat control is interrupted to allow the 
pressure to be controlled, and the valve closes slowly, trying to limit the 
evaporation temperature. As the action is integral, it depends directly on 
the difference between the evaporation temperature and the activation 
threshold. The more the evaporation temperature increases with 
reference to the MOP threshold, the more intensely the valve will close. 
The integration time indicates the intensity of the action: the lower the 
value, the more intense the action.

t

t

t

t

OFF

ON

ALARM

OFF

ON

PID

OFF

ON

MOP

MOP_TH - 1

MOP_TH

T_EVAP

D

Fig. 6.c

Key:

T_EVAP Evaporation temperature

MOP_TH MOP threshold

PID

PID superheat control

ALARM

Alarm

MOP

MOP protection

t

Time

D

Alarm timeout

 

Important:

 the MOP threshold must be greater than the rated 

evaporation temperature of the unit, otherwise it would be activated 
unnecessarily. The MOP threshold is often supplied by the manufacturer 
of the compressor. It is usually between 10 °C and 15 °C.

If the closing of the valve also causes an excessive increase in the suction 
temperature (S2) above the set threshold – set via parameter (C7), not 
on the display - the valve will be stopped to prevent overheating the 
compressor windings, awaiting a reduction in the refrigerant charge. If 
the MOP protection function is disabled by setting the integral time to 
zero, the maximum suction temperature control is also deactivated.

Par. Description

Def.

Min.

Max. U.M.

C7 MOP protection: disabling threshold

30
(86)

-85 
(-121)

200
(392)

°C (°F)

At the end of the MOP protection function, superheat control restarts 
in a controlled manner to prevent the evaporation temperature from 
exceeding the threshold again.

Содержание EVD ice

Страница 1: ...H i g h E f f i c i e n c y S o l u t i o n s EVD ice NO POWER SIGNAL CABLES TOGETHER READ CAREFULLY IN THE TEXT User manual Superheat control for unipolar electronic expansion valve...

Страница 2: ......

Страница 3: ...not use corrosive chemicals solvents or aggressive detergents to clean the device do not use the product for applications other than those specified in the technical manual All of the above suggestio...

Страница 4: ......

Страница 5: ...2 Special control function smooth lines 14 5 3 Service parameters 14 6 PROTECTORS 15 6 1 Protectors 15 7 PARAMETERS TABLE 17 8 NETWORK CONNECTION 18 8 1 RS485 serial configuration 18 8 2 Network conne...

Страница 6: ......

Страница 7: ...om controllers 1 1 Models P N Description EVDM011R3 EVD ice 115 230 V E2V stator display EVDM011R1 EVD ice 115 230 V E2V stator display Ultracap module connector EVDM011R4 EVD ice 115 230 V E3V stator...

Страница 8: ...portant install EVD ice on the evaporator away from the places where ice forms connect the power and serial cables in the IP65 junction box for assembly of the E2V E3V valve see the ExV system guide 0...

Страница 9: ...Regulator P T EEV M Condenser Electrical panel Compressor Condenser unit Evaporator unit Solenoid valve IP65 L N Fig 2 d WITHOUT SOLENOID VALVE WITH ULTRACAP MODULE COLD ROOM IN COLD ROOM OUT COLD RO...

Страница 10: ...d pressure probe see the chapter on Commissioning 2 connectthepowercableandthedigitalinputcable forthemaximum length see the technical specifications 3 poweronthedriver thedisplaywilllightup andthedri...

Страница 11: ...than 9 are displayed in two steps first the sign then the tens and units GASType Mode Super Heat GASType Mode Super Heat 123 GASType Mode Super Heat GASType Mode Super Heat 99 Fig 3 b Note the decima...

Страница 12: ...Superheat set point GASType Mode Super Heat 7 Press PRG Set for 2 seconds to exit the commissioning procedure and start control The standard display is shown 4 2 Parameters first configuration Import...

Страница 13: ...through the nozzle corresponds to the flow rate required by the compressor In this way the evaporation process will take place along the entire length of the evaporator and there will be no liquid at...

Страница 14: ...ol temperature approaches the set point the Smooth_line parameter is used to prevent the valve from closing by reducing the evaporator s cooling capacity In order to use this function the digital inpu...

Страница 15: ...activation threshold depending on the operating conditions of the controlled unit this is set in Service programming mode integration time which determines the intensity if set to 0 the protector is...

Страница 16: ...refrigerant charge or when there are sudden variations in the load The protector is also useful in multiplexed systems showcases as allows all the utilities to be enabled at the same time without cau...

Страница 17: ...Po Valve opening 0 100 A 1 0 R CP PID proportional gain 15 0 800 A 11 10 R W ti PID integral time 150 0 999 s I 17 144 R W C1 LowSH protection threshold 5 9 5 9 Superheat set point K F A 12 11 R W C2...

Страница 18: ...00 2 stop bit parity odd 15 4800 1 stop bit parity odd 16 9600 1 stop bit parity odd 17 19200 1 stop bit parity odd 2 0 17 Important all controllers connected in a serial network need to be set with t...

Страница 19: ...RS485 rear connector Offline Device model Online Offline Device setup Read instant values of control parameters Select Load to load a list of project parameters hex modify and save a new project Setup...

Страница 20: ...iguration page parameters p_GAS_TYPE refrigerant and p_SUPER_MAIN_REGULATION type of control b on the Configuration page parameter p_SH_SET Fig 8 m 3 Savethelistofparameterswithanewname forexample NEW...

Страница 21: ...om dew_f_l Dew f low 17239 32768 32767 I 35 162 R W Net_alarm Network alarm 0 0 1 D 1 0 R all E6 Emergency_closing_alarm Mains power failure 0 0 1 D 2 1 R all E5 S1_alarm Probe S1 alarm 0 0 1 D 3 2 R...

Страница 22: ...r or when reaching the control set point It can also occur when opening the digital input which involves closing the valve or in the event of a probe alarm In general it can be said that the electroni...

Страница 23: ...a power failure proceed as follows remove the valve stator set the PID proportional gain 0 The valve will remain stopped at the initial opening position set by corresponding parameter Retrieve physica...

Страница 24: ...ent of probe or valve malfunctions to protect the compressor using the relay to control the solenoid valve or to simply signal a possible risk In fact incorrect measurement of the evaporation pressure...

Страница 25: ...inets only Decrease the value of the Valve opening at start up parameter on all the utilities making sure that there are no repercussions on the control temperature Liquid returns to the compressor on...

Страница 26: ...the valve by placing it in manual control and closing or opening it com pletely One complete opening must bring a decrease in the superheat and vice versa If the movement is reversed check the electri...

Страница 27: ......

Страница 28: ...EL INDUSTRIES HeadQuarters Via dell Industria 11 35020 Brugine Padova Italy Tel 39 049 9716611 Fax 39 049 9716600 e mail carel carel com www carel com Agenzia Agency EVD ice 0300038EN rel 1 1 23 04 20...

Отзывы: