NOTE: Password to enter factory settings menu is 1111. If scheduling is On, occupied and
unoccupied settings will be available for some parameters.
FACTORY SETTINGS
UNIT OPTIONS
ROOM OVERRIDE
ON/OFF
DEFAULT: OFF
EXHAUST CONTACTOR
NONE (DEFAULT),
BEFORE AIRFLOW, AFTER AIRFLOW
OCC/UNOCC
EXHAUST ON SMOKE
ON/OFF
DEFAULT: OFF
ENABLE
UNIT HEATERS
ON/OFF
DEFAULT: OFF
CABINET
DRAIN
CRANKCASE
ON/OFF
DEFAULT: OFF
ON/OFF
DEFAULT: OFF
AUX INPUT
UNIT OFF, BOTH OFF (DEFAULT),
COOL OFF, HEAT OFF, SET BACK
MODE
OUTDOOR RESET
ENABLE
ON/OFF
DEFAULT: OFF
DD WHEEL SIZE
SIZE
MODELS: 11,13, 15, 18, 20, 24, 30,
36, 16Z,18Z, 20Z, 22Z, 25Z, 28Z
DYNAMIC SET POINT
ENABLE
ON/OFF
DEFAULT: OFF
CO2 CONTROL CONFIG
OVERRIDE
OFF (DEFAULT), BLOWER,
DAMPER
DEHUMID INPUT
ENABLE
REHEAT DEFAULT: ON
NO REHEAT DEFAULT: OFF
THRESHOLD
OFF (DEFAULT), BLOWER,
DAMPER
DURATION
RANGE: 1-16 H
DEFAULT: 1 H
OCC OVRD DURATION
LIMIT SP ADJUST
LIMIT
RANGE: 0-100°F/0-55°C
DEFAULT: 5°F/3°C
TEMP OVRD DURATION
DURATION
RANGE: 1-16 H
DEFAULT: 1 H
PID CONFIG
DO NOT ADJUST
SETTINGS
SENSOR OFFSETS
DSCHRG DISP
SPACE DISP
DSCHRG RH
SPACE RH
RANGE: 0-20°F/0-11°C
DEFAULT: 0°F/0°C
RANGE: 0-20°F/0-11°C
DEFAULT: 0°F/0°C
RANGE: 0-30%
DEFAULT: 0%
RANGE: 0-30%
DEFAULT: 0%