68
OPTION SET POINTS
ROOM OVERRIDE
FIRESTAT SET POINTS
FREEZESTAT SET POINT
CAB HEAT SET POINT
RANGE: 100-300°F/38-149°C
DEFAULT: 135°F/57°C
RANGE: 100-300°F/38-149°C
DEFAULT: 240°F/116°C
RANGE: (-40)-75°F/(-40)-24°C
DEFAULT: 35°F/2°C
RANGE: 0-40°F/(-18)-4°C
DEFAULT: 0°F/-18°C
RANGE: 40-150°F/4-66°C
DEFAULT: 90°F/31°C
INTAKE
DISCHARGE
FREEZESTAT
CAB HEAT
USER SETTINGS
TEMP SET POINTS
DRAIN HEAT SET POINT
RANGE: 35-45°F/2-7°C
DEFAULT: 35°F/2°C
DRAIN HEAT
OVERHEAT SET POINT
RANGE: 60-120°F/15-49°C
DEFAULT: 80°F/27°C
OVERHEAT
ECONOMIZER SETTINGS
TEMP SETTINGS
TEMP OCC/UNOCC
RANGE: 0-80°F/(-17)-27°C
DEFAULT: 60°F/16°C
BAND OCC/UNOCC
RANGE: 0-20°F/0-11°C
DEFAULT: 5°F/3°C
TOTAL BAND SETTINGS
RH OCC/UNOCC
BAND OCC/UNOCC
RANGE: 0-20°F/0-11°C
DEFAULT: 5°F/3°C
RANGE: 0-90%
DEFAULT: 50%
OA RESET LOW
OA RESET HIGH
RANGE: 35-110°F/7-43°C
DEFAULT: 45°F/7°C
RESET LOW
RANGE: 35-110°F/7-43°C
DEFAULT: 75°F/7°C
RESET HIGH
RESET HEAT DISCHARGE
RESET COOL DISCHARGE
RANGE: 40-150°F/4-65°C
DEFAULT: 90°F/32°C
HEAT DISCH
RANGE: 35-110°F/7-43°C
DEFAULT: 50°F/32°C
COOL DISCH
RESET HEAT SPACE
RESET COOL SPACE
RANGE: 40-150°F/4-65°C
DEFAULT: 90°F/32°C
HEAT SPACE
RANGE: 35-110°F/7-43°C
DEFAULT: 50°F/32°C
COOL SPACE
SCHEDULING
SCHEDULING TIMES
COPY SCHEDULE
START A/B/C - UNOCC/TIME
END A/B/C - UNOCC/TIME
MONDAY - SUNDAY
COPY FROM “DAY”
COPY TO “DAY”/WEEKDAYS/ALL
FAN SPEED (VFD)
FREQ
RANGE: MIN - MAX VFD HZ
DEFAULT: 60 HZ
FAN SPEED (ECM)
RATE OCC/UNOCC
RANGE: MIN - MAX PWM %
DEFAULT: 100%
OUTDOOR AIR SETTINGS
PERCENT or VOLTAGE
OCC/UNOCC
RANGE: 0-100% or 0-10V
DEFAULT: MIN % or MIN V
COMPRESSOR FREQ
FREQ
RANGE: MIN - MAX HZ
DEFAULT: VARIES
VZH044 and smaller: Range 30-200Hz.
Default 200Hz
VZH052 - VZH065: Range 50-330Hz.
Default 330Hz
VZH088 and larger: Range 50-330Hz.
Default 200Hz