69
USER SETTINGS
ACTIVE FAULTS
DISPLAYS ACTIVE FAULTS
FAULT HISTORY
DISPLAYS UP TO
20 FAULTS
RESET LOCKOUTS
RESETS ACTIVE
LOCKOUTS
PRESSURE CONFIG
RANGE: - 0.0” - HIGH
DEFAULT: 0.00 "WC
LOW (OCC/UNOCC)
HIGH (OCC/UNOCC)
RANGE: LOW - 5.0
DEFAULT: 0.10 "WC
DYNAMIC SP DIFF
RANGE: 0-50°F/0-25°C
DEFAULT: 10°F/5°C
DYNAMIC SP OFFSET
RANGE: (-20)-20°F/(-11)-11°C
DEFAULT: 1°F/1°C
DYNAMIC HEAT OA
RANGE: 0-110°F/(-18)-43°C
DEFAULT: 30°F/-1°C
DYNAMIC COOL OA
RANGE: 35-110°F/2-43°C
DEFAULT: 80°F/27°C
DRY MODE CONFIG
RH OCC/UNOCC
DISCHARGE OCC/UNOCC
INTAKE OCC/UNOCC
RANGE: 20-80%
DEFAULT: 50%
RANGE: 40-150°F/4-66°C
DEFAULT: 90°F/13°C
RANGE: 35-110°F/2-43°C
DEFAULT: 45°F/7°C
CO2 CONTROL CONFIG
PPM LOW (OCC/UNOCC)
RANGE: 0 PPM - PPM HIGH
DEFAULT: 500 PPM
PPM HIGH (OCC/UNOCC)
RANGE: PPM LOW - 2,000 PPM
DEFAULT: 1,000 PPM
SENSOR MIN
SET RANGE TO CO2 SENSOR
MIN SETTING
SENSOR MAX
SET RANGE TO CO2 SENSOR
MAX SETTING
ERV SETTINGS
ERV EXHAUST FAN
ERV WHEEL CLEANING
SPEED OCC/UNOCC
RANGE: MIN - MAX FAN SPEED
DEFAULT: 75%
STATE
ON/OFF
DEFAULT: OFF
STATE ON
CLEANING ACTIVE
ENDS IN 60 S
MAN COND FAN SPEED
HEAT
COOL
RANGE: 0-100%
DEFAULT: 100%
RANGE: 0-100%
DEFAULT: 100%
Adjust OCC only if on schedule.
Adjust OCC only if on schedule.
ERV WHEEL SPEED
SPEED OCC/UNOCC
RANGE: 20-100%
DEFAULT: VARIES BY MODE
DIFF
OFFSET
HEAT OA
COOL OA
PPM LIMIT
RANGE: 1 - 2,499 PPM
DEFAULT: 1,000 PPM