FACTORY SETTINGS
NOTE: Password to enter factory settings menu is 1111
• PS KP –
Proportionally constant value for static pressure measured in V/sec.
• PS Hyst –
Building pressure must go above or below hysteresis value for fan adjust accordingly.
• S REF KP –
Proportionally constant value for supply fan pressure measured in V/sec. Only
displayed when Exhaust Fan Control is set to supply reference.
• S REF DB – Defines the limits the unit will adjust to keep supply fan reference. Only
displayed when Exhaust Fan Control is set to supply reference.
• S REF SP –
If the pressure difference between the supply and exhaust is greater/less than this set
point, the MUA board will attempt to adjust the output voltage until it matches the supply reference
set point.
• EF Comm –
ERV communication loss, dictates functionality of exhaust fan when communication is
lost between exhaust fan and ERV.
• Defrost Control –
Optional monitoring and wheel control that will keep frost from forming, or melt the
frost if it has formed.
• Mode
–
Selectable activation type for frost control.
• OA Temp SP –
If Temp/RH defrost is selected, the OA temp must be below set point for the ERV to
enter defrost mode.
• EA Temp SP –
If Temp/RH defrost is selected, the EA temp must be below set point for the ERV to
enter defrost mode.
• RA RH SP–
If Temp/RH defrost is selected, the RA RH must be above set point for the ERV to enter
defrost mode.
• On Time –
Time setting in which the enthalpy wheel spins at the defrost wheel speed setting.
• Off Time –
Time setting the ERV cannot activate into a defrost cycle after a cycle has completed.
• Speed –
Adjustable speed which the user may set the enthalpy wheel speed during defrost cycle.
• Wheel Cleaning –
Wheel cleaning settings.
• Mode –
Selectable activation modes for wheel cleaning cycle.
• On Time –
Amount of time the cleaning cycle is on when activated.
• Off Time –
Amount of time that if the ERV is continuously off will activate a cleaning cycle.
• Min OA Damper Pos –
Adjustable set point for the damper to activate.
• Staging Control
– Adjustable time value that corresponds to the staging of the ERV and the
Dedicated Outdoor Air System (DOAS) unit.
Occupancy Config
• Scheduling
– This menu is where scheduling may be turned On or Off. Default is Off.
• Override
– Allows the user to override the current occupied settings. This is an On/Off option. Default
is Off.
Unit Options
• Board Config
• Unit Address –
Modbus address of the MUA board.
• Startup Timer –
Time upon power-up where the board will sit idle.
• Temp Units –
Allows the user to set temperature range. Changing between the two will reset all set
points. The board will reset as well.
• HMI Config
• Number
– Number of HMIs connected to the MUA board. Must always be at least one.
• Screensaver –
This is an On/Off menu. Default is set to On. If set to Off, the home screen will not
time out to the screensaver.
• Average HMI
– If there are multiple space HMIs connected, this menu allows you to select which
will be included in the space temperature and relative humidity averaging. If a thermistor or
relative humidity sensor is connected into the ST screw terminals, it will automatically be
averaged into any HMIs included.