Flame Safety Control (FSC-01)
The FSC is located in the main control cabinet.
1. Verify wiring and connections are properly connected (
).
2. Turn the unit ON. Use the HMI to set the unit in test mode.
• Service > Test Menu > Test Heating > Run Low Fire Test > Stages All
• Refer to
“Flame Safety Control (FSC)” on page 83
for operation of sequence.
Determine the symptom below:
3. Turn the unit ON. If the LED is blinking, verify the fault:
• Steady ON = Internal controller failure
• 1 flash = Airflow fault. 2 flashes = Flame without call for heat. 3 flashes = Ignition lock out
Figure 63 - FSC Wiring
Symptom
Action
Control does not start
• Check wiring.
• Check for a
24V AC
transformer failure.
• Check circuit breaker.
• Check LED light.
Thermostat ON – no spark
• Check wiring to thermostat input (TH).
• Faulty thermostat.
• Check LED light.
Blower ON – no Trial For Ignition (TFI) after purge
delay
• Check wiring.
• Check for flame fault.
• Air flow fault, check tubes and connections to
MUA Board airflow switch.
• Check connection at PSW terminal.
• Faulty control (Check voltage between L1 and
IND. There should be
24V AC
).
Valve ON – no spark during TFI
• Check wiring.
• Shorted ignitor electrode.
• Check cable to ignitor.
Spark ON – valve OFF
• Check wiring.
• Valve coil open.
• Check voltage at V1.
Flame during TFI – no flame sensed after TFI
• Check flame rod position.
• Check cable to flame rod.
• Poor ground connection at burner.
• Poor flame.