Installation Manual
February 2024 • Rev. 1.1
Specifications
See power supply notes in Appendix section for more information.
Controller Power Requirement
Max. Current (including 4 proximity readers with 100 mA each) ……… 12VDC/1A
Temperature Range
Operating ……………………………………………………………………………….. 0˚C to 60˚C
Relative Humidity
Operating ………………………………………………………..……………………… 20% to 80%
Auto Resettable Fuses
Webster 64 Main 12V DC………………………………………………………………………1 A
Each Reader Pair ……………………………………………………………………………………1 A
Output Relays
All Relays (8 per panel) Form ‘C’ …………………………………SPDT 6 A @ 30 VDC
Inputs per Provisioned Doors (Supervised or Non-Supervised)
Door Contact (2 per Webster 64) ………………………Requires normally closed contact
(On/Off door switch)
Exit Button (2 per Webster 64) ………………..…………Requires
normally open contact
(Momentary push button switch)
Reader Cable
Wiegand Readers .......................................... 6 conductor (twisted pair not required)
.................................................................................
22 AWG, overall shield
...........................................................................
152 m [500
ft] max. Length
NOTE
:
Consult reader specifications as 18-gauge wire may be required for power
Dimensions & Weight
Webster 64 Enclosure …………………………………………..4.6” (W) x 4.9” (H) x 2.0” (D)
[11.7 cm (W) x 12.4 cm (H) x 5.1 cm D)]
Enclosure plus Controller Weight ....................................................... 500 g [17.6 oz]
Содержание Webster 64
Страница 1: ...Webster 64 Controller INSTALLATION MANUAL September 2023...
Страница 13: ...Webster 64 Page 13 of 32 Installation Manual February 2024 Rev 1 1 Figure 6 Non Supervised...
Страница 14: ...Webster 64 Page 14 of 32 Installation Manual February 2024 Rev 1 1 Figure 7 Supervised...
Страница 32: ...Webster 64 Page 32 of 32 Installation Manual February 2024 Rev 1 1...