Webster 64
Page 23 of 32
Installation Manual
February 2024 • Rev. 1.1
9.
The factory default or current password for a new Webster 64 panel is
Cansec
.
The password must be changed to something else other than
Cansec
.
10.
Click
Save
. The panel saves the new settings and reboots for the settings to take
effect.
USB IP CONFIGURATION TOOL
Important
:
Shutdown Push Button (PB1) must be used to avoid data corruption on the
Webster 64 controller
.
1.
If the Webster 64 controller is powered on, press and hold the PB1 button for a
period of 5 to 8 seconds and proceed to step 2. Otherwise, proceed to step 4.
2.
When the PLM LED on the front of the Webster 64 controller begins a rapid flash,
release the Shutdown PB1 button.
Figure 19
Figure 20