MAPMINI
Page 18 of 28
Installation Manual
September 2021 • Rev. 1.4
Note 2:
6 Amp Relay Rating
Maximum current that can be switched reliably when connected to a ‘non-inductive load’ up to
30VDC. Electric strikes and magnetic locks are considered ‘inductive loads’. It is important to
have diode or MOV attached at the locking device to remove the CEMF pulse that is generated
when switching an ‘inductive load’. It is advisable to use a 50% switch factor or 3 amps as the
maximum switching current for longer relay life. An external relay should be used on larger
voltage and current requirements
.
MAPMINI SYSTEM INDICATORS
12VDC POWER LED
: ON indicates 12 volts DC is connected.
First Access Mode
:
Mode indicator: MAPMINI emits 1 beep after powered up.
Webster Mode
:
Mode indicator: MAPMINI emits 2 beeps after powered up.
CloudACS Mode
:
Mode indicator: MAPMINI emits 3 beeps after powered up.
SHDN LED
:
Flashing GREEN – PLM (Panel Logic Module) is waiting for a connection from
the host via Ethernet.
Steady GREEN – PLM (Panel Logic Module) is connected to a host via
Ethernet.
OFF – PLM (Panel Logic Module) is powered off.
IMPORTANT:
In some jurisdictions, the use of a UL approved power supply and
connection to the fire alarm system for emergency release may be required. Installers
should contact the local authority having jurisdiction to verify the specific
requirements. Also, a building permit may be required in some jurisdictions for the
installation of magnetic locks.