MAPMINI 

Page 18 of 28 

 

Installation Manual 

September 2021 • Rev. 1.4 

Note 2:

 

6 Amp Relay Rating 

 

Maximum current that can be switched reliably when connected to a ‘non-inductive load’ up to 
30VDC. Electric strikes and magnetic locks are considered ‘inductive loads’. It is important to 
have diode or MOV attached at the locking device to remove the CEMF pulse that is generated 
when switching an ‘inductive load’. It is advisable to use a 50% switch factor or 3 amps as the 
maximum switching current for longer relay life. An external relay should be used on larger 
voltage and current requirements

 

 

MAPMINI SYSTEM INDICATORS 

 

12VDC POWER LED

: ON indicates 12 volts DC is connected. 

First Access Mode

 

Mode indicator: MAPMINI emits 1 beep after powered up. 

Webster Mode

 

Mode indicator: MAPMINI emits 2 beeps after powered up. 

CloudACS Mode

 

Mode indicator: MAPMINI emits 3 beeps after powered up. 

  

SHDN LED

:   

 

Flashing GREEN – PLM (Panel Logic Module) is waiting for a connection from 
the host via Ethernet.   

 

Steady GREEN – PLM (Panel Logic Module) is connected to a host via 
Ethernet. 

 

OFF – PLM (Panel Logic Module) is powered off. 

IMPORTANT:

 In some jurisdictions, the use of a UL approved power supply and 

connection to the fire alarm system for emergency release may be required. Installers 
should contact the local authority having jurisdiction to verify the specific 
requirements. Also, a building permit may be required in some jurisdictions for the 
installation of magnetic locks.

 

Содержание MAPMINI Controller

Страница 1: ...MAPMINI Controller INSTALLATION MANUAL September 2021...

Страница 2: ...Contact Wiring 12 Lock Output and Multi Function Relay Wiring 13 Input and Output Point Wiring 15 Appendix 17 MAPMINI System Indicators 18 Power Connector 19 SHUTDN Shutdown Button 19 IP Address Reset...

Страница 3: ...and data cannot be shared between modes The availability of the general purpose Input and Output points depends on the number of doors provisioned for the controller The MAPMINI allows for 100 000 in...

Страница 4: ...Current including 1 proximity reader with 100 mA 12VDC 1A Temperature Range Operating 0 C to 60 C Relative Humidity Operating 20 to 80 Auto Resettable Fuses MAPMINI Main 12V DC 1 A Reader Pair Entry E...

Страница 5: ...E Consult reader specifications as 12 gauge wire may be required for power Dimensions Weight MAPMINI Controller 4 6 W x 3 35 L x 1 5 D 11 6 cm W x 8 5 cm L x 3 8 cm D MAPMINI Enclosure 9 5 W x 13 L x...

Страница 6: ...ginally installed cable or missing required shield connections may result in high frequency noise on the data lines creating misreads This Wiegand misread issue is more evident on longer Wiegand reade...

Страница 7: ...MAPMINI Page 7 of 28 Installation Manual September 2021 Rev 1 4 MAPMINI Controller Layout Figure 1...

Страница 8: ...e no lock relay and no multi function relay Electrical Information 1 The MAPMINI utilizes a mini computer and must be operated using a battery backed up power supply to protect the hardware system fi...

Страница 9: ...IP address automatically DHCP However it can be optionally set to a static IP address or reset if necessary See Appendix section for more information Mechanical Information 1 If required the MAPMINI m...

Страница 10: ...up just for the MAPMINI Controller and a separate power supply which can be sized to supply the amount of current that the attached high current device e g lock will require Figure 5 Mode Indicator Af...

Страница 11: ...entry reader ENTRY AND EXIT READER WIRING Figure 6 Exit Reader D1 White of exit reader connects to D0 Green of entry reader D0 Green of exit reader connects to D1 White of entry reader Figure 7 Exit...

Страница 12: ...XIT BUTTON AND DOOR CONTACT WIRING Note Both door contact and exit button inputs have voltage present on the circuits Only connect dry contact devices to these inputs Figure 8 Figure 9 The RTE REX can...

Страница 13: ...ly one of the following options Alarm Shunt factory default Shunt the alarm system before opening lock Door Held Open Door has been left open Forced Entry Door opened without access granted or exit bu...

Страница 14: ...risdiction to verify the specific requirements Also a building permit may be required in some jurisdictions for the installation of magnetic locks Figure 11 See Note 2 in Appendix section for 6 Amp re...

Страница 15: ...mber 2021 Rev 1 4 INPUT AND OUTPUT POINT WIRING The MAPMINI can be provisioned for all I O which allows for 2 input points and 2 output points to be used There is no door provisioned in this mode Inpu...

Страница 16: ...MAPMINI Page 16 of 28 Installation Manual September 2021 Rev 1 4 Output Wiring Figure 13...

Страница 17: ...7AH batteries 13 5 x 13 x 3 25 342 9mm x 330 2mm x 82 55mm 6 65 lbs 3 02 kg 12 24 VDC selectable output 6 Amp Enclosure Style Power Supply with Backup Battery Charger Eight individual Class 2 rated po...

Страница 18: ...ER LED ON indicates 12 volts DC is connected First Access Mode Mode indicator MAPMINI emits 1 beep after powered up Webster Mode Mode indicator MAPMINI emits 2 beeps after powered up CloudACS Mode Mod...

Страница 19: ...N LED near the SHUTDN button begins a rapid green ON OFF flash then release the pushbutton The system will start a proper shutdown This will take 15 to 20 seconds 2 Wait untill the status SHDN LED exc...

Страница 20: ...e 20 to 45 seconds after which the controller will reset all of its configurations to factory default with DHCP enabled Existing database will not be reset or erased 3 Note The end of the reboot cycle...

Страница 21: ...IP address range ready to be scanned However the IP address range can be manually modified accordingly 7 Click Scan to scan the network for all possible connected MAPMINI panels 8 Double click on one...

Страница 22: ...ns for diagnosis and updating are not limited by this Trusted Host IP 10 The factory default or current password for a new unconfigured MAPMINI panel is Cansec The password must be changed to somethin...

Страница 23: ...uence which takes about 30 to 40 seconds When complete the MAPMINI controller will emit a series of beeps 1 beep 2 beeps or 3 beeps to indicate its provisioned mode First Access Webster or CloudACS re...

Страница 24: ...ual September 2021 Rev 1 4 MAPCFG txt created by the MAPMINI controller during boot up sequence If the file is not present repeat from step 1 Otherwise proceed to step 7 7 A similar file will be displ...

Страница 25: ...eway where the host computer is connected to SrvPort 5000 Factory default server port It s suggested to leave it as default DiagPort 5001 Factory default diagnostic port It s suggested to leave it as...

Страница 26: ...rite USB INIT DONE to indicate that the initialization has been done 8 Obtain all IP address information from IT personnel and modify the file accordingly Remove the line USB INIT DONE and save the fi...

Страница 27: ...exit button event A message will be transmitted to the host software if the panel is online DOOR HELD OPEN OUTPUT The MF multifunction relay when configured as Door Held Open will be activated if the...

Страница 28: ...st followed by a one second pulse on this MF relay which is used to trigger the door operator DOOR OPERATOR OUTPUT HANDICAP CARDS ONLY The MF multifunction relay when configured as Door Operator_HC wi...

Отзывы: