Hold 63: LCI OFF (Load Control Input)
Hold 67: ILK OFF (High Limit, Gas Pressure Switch, Air Switch)
Alert 303: Abnormal Recycle: ILK off during drive to Purge
Alert 304: Abnormal Recycle: ILK off during Measured purge time
Alert 305: Abnormal Recycle: ILK off during Drive to Pre-igntion
Alert 306, 307: Abnormal Recycle: ILK off during Pre-ignition
Alert 308: Abnormal Recycle: ILK off during Main Flame
Alert 309: Abnormal Recycle: ILK off during Ignition Period
Alert 460: LCI lost in run
This error occurs when one of more of the boiler safety switches are in an open condition when it is to be in a closed condition
before the ignition sequence is allowed to proceed.
Flow Switch
Gray
Check flow switch
Green
Open
Check flow switch paddle
Closed
Check blocked
flue switch
Open
Check vent & inlet for
obstruction
High Limit
Gray
Check high limit
Open
Reset high limit
Green
Gas Pressure Switch
Gray
Low gas switch
Open
Check inlet gas pressure
> 3” w.c.
Green
Closed
High gas switch
Open
Check inlet gas pressure
< 14” w.c.
Air Switch
Gray
Green
Check air proving
switch
Open
Turn set screw CCW 1/2
to 1-1/2 turns
Check J5-2
connector
SOLA for
24Vac signal
Proceed to
ignition sequence
Содержание DFH/W1100
Страница 2: ......
Страница 40: ...35...
Страница 71: ...66 PART 12 EXPLODED VIEW...
Страница 72: ...67 3 44 10 45 46 47 28 31 26 52 57 58 59 54 60 61 SOLA Control Panel 39 4...
Страница 82: ...77 PART 13 ELECTRICAL DIAGRAMS...
Страница 83: ...78...
Страница 85: ...80...
Страница 86: ...81...
Страница 87: ...82...