The following steps are performed at the factory and verifying on site will
be sufficient:
6)
Select
Pump Configuration
7)
Press
[Advanced Options >>]
8)
Press the to arrive at
Central Heat Pump
or
DHW Pump
9)
On Options: Local burner demand
10)
On Options: Local Lead Lag Service Active
11)
Force On: Outlet high limit
Master Boiler, System Sensor
Description
Electrical Connection(s)
Programming Instructions
•
Master boiler system sensor
configuration
1)
Press
and
2)
Press
[Sensor Configuration]
3)
Select
S5 (J8-11) Sensor
4)
Connector Type:
10K NTC Single Non-Safety
5)
The control will proceed into a Lockout 2 condition
6)
Press
[Verify]
>
[Begin]
>
[Yes]
7)
Press the reset button on the ignition control within the alotted time