![Camus Hydronics DFH/W1100 Скачать руководство пользователя страница 34](http://html1.mh-extra.com/html/camus-hydronics/dfh-w1100/dfh-w1100_installation-operation-and-service-manual_490905034.webp)
29
DFH
Modulation: Boiler Inlet, Boiler Fixed Setpoint Operation (Standalone)
Description
Electrical Connection(s)
Programming Instructions
•
Boiler operates at a fixed
setpoint
•
Modulates on boiler inlet
sensor (default)
•
Heat demand is generated
when Remote Operator is
closed.
1)
Press
and
2)
Press
[CH – Central Heat Configuration]
3)
Press the to arrive at
Setpoint
4)
Select
Setpoint source: Local
5)
Enter desired
Setpoint
6)
Place toggle switch to
REMOTE
for remote enable operation (if required)