Modulation: Boiler Inlet, Fixed Setpoint Operation (Standalone, Lead Lag)
Description
Electrical Connection(s)
Programming Instructions
•
Boiler operates at a fixed
DHW setpoint
•
Modulates on boiler inlet
sensor (default)
•
Heat demand is generated
when Remote Operator is
closed.
DHW Sensor/ Stat, if required.
1)
Press
and
Inlet Sensor operation
2)
Press
[DHW – Domestic Hot Water Configuration]
3)
Select
Demand Switch: Modulation sensor only
4)
Select
Modulation sensor: Inlet Sensor
. Proceed to Step 12
DHW Sensor/Stat operation
1)
Press
[Sensor Configuration]
2)
Select
S6S7 (J9-1,3) Sensor
:
10K NTC Single Non-Safety
3)
The control will proceed into a Lockout 2 condition
4)
Press
[Verify]
>
[Begin]
>
[Yes]
5)
Press the reset button on the ignition control within the alotted time
DHW Sensor operation
5)
Press
[DHW – Domestic Hot Water Configuration]
6)
Select
Demand Switch: Modulation sensor only
7)
Select
Modulation sensor: DHW Sensor
. Proceed to Step 12
DHW Stat operation
8)
Press
[DHW – Domestic Hot Water Configuration]
9)
Select
Demand Switch: Modulation sensor only
10)
Select
Modulation sensor: DHW (S6) switch & inlet sensor
11)
Enter desired
Setpoint
12)
Place toggle switch setting to
REMOTE
for remote operation (if required)
Содержание DFH/W1100
Страница 2: ......
Страница 40: ...35...
Страница 71: ...66 PART 12 EXPLODED VIEW...
Страница 72: ...67 3 44 10 45 46 47 28 31 26 52 57 58 59 54 60 61 SOLA Control Panel 39 4...
Страница 82: ...77 PART 13 ELECTRICAL DIAGRAMS...
Страница 83: ...78...
Страница 85: ...80...
Страница 86: ...81...
Страница 87: ...82...