execute. Data logger security may need to be unlocked before transparent mode can be
activated.
Transparent mode is entered while the computer is communicating with the data logger through
a terminal emulator program such as through Device Configuration Utility or other data logger
support software. Keyboard displays cannot be used. For how-to instructions for communicating
directly with an SDI-12 sensor using a terminal emulator, watch this
To enter the SDI-12 transparent mode, enter the data logger support software terminal emulator:
1. Press Enter until the data logger responds with the prompt
CR6>
.
2. Type
SDI12
at the prompt and press Enter.
3. In response, the query
Select SDI12 Port
is presented with a list of available ports.
Enter the port number assigned to the terminal to which the SDI-12 sensor is connected,
and press Enter. For example,
1
is entered for terminal C1.
4. An
Entering SDI12 Terminal
response indicates that SDI-12 transparent mode is
active and ready to transmit SDI-12 commands and display responses.
The terminal-mode utility allows monitoring of SDI-12 traffic by using the watch command
(sniffer mode). Watch an instructional
or use the following instructions.
7. Communications protocols
105