NOTE:
Wait for the instructions to prompt for all entries. By default, if no changes have been made
by 60 seconds, the program will time out and exit the calibration process. Increase the
EntryDelay_Seconds value if more time is needed to input information. Changing the
EntryDelay_Seconds variable to 120 will increase the time out delay to 2 minutes.

Occasionally the calibration routine will time out for no apparent reason. If this happens,
restart the calibration of the failed lighting loop.

The calibration procedure is done by editing the Public Table.

1. Instruct the light controller to turn on the runway lighting loop to be calibrated to the

lowest light setting

2. Set Start_Calibration to true (1 or -1).

3. Type the Runway Number and press Enter.

4. Type e for the runway edge or c for center light loop to be calibrated and press Enter.

5. Type the measured Off light level meter reading value in amps in the Low_Current_

Measurement variable and press Enter.

NOTE:
Meter reading must be greater than 0.00. Therefore, enter 0.001 if the meter reading is
0.00.

The FieldcalMode variable will change to 3 after the first input value is processed, and the
Calibration_Message will request the lighting loop high value.

6. Instruct the light controller to turn on the runway lighting loop to be calibrated to the

Highest light setting.

7. Type the measured high light level meter reading value in amps into the High_Current_

Measurement variable and press Enter. The FieldcalMode variable will change to 6 when
calibration has completed. The program will restart and place the values into the constants
table. The

Device Configuration

utility may need to be reconnected.

8. Turn OFF the runway lights.

9. Repeat the previous steps for each runway lighting loop.

The calibration data is contained in the constants table RLIMCalValues.

AeroX Light

13

Содержание AeroX Light

Страница 1: ...Revision 04 2023 Copyright 2023 Campbell Scientific Inc AeroX Light Runway Light Intensity Monitor RLIM PRODUCT MANUAL...

Страница 2: ...cs 4 5 Configuration 6 5 1 Power configuration 6 5 2 Hardware configuration 6 5 3 Data logger configuration 9 5 3 1 Disable unused services 10 5 3 2 Edit configuration settings 12 5 4 Current transduc...

Страница 3: ...ighting loop using clamp on current transducers Each current transducer outputs from 4 to 20 mA of current proportional to the amount of current in the lighting loop Typically each airport runway has...

Страница 4: ...this manual l Although the AeroX Light is rugged it should be handled as a precision scientific instrument 3 Initial inspection l Upon receipt of the AeroX Light inspect the packaging and contents fo...

Страница 5: ...aintains power to AeroX Light for a minimum of 4 hours Operating temperature 40 to 85 C Clamp on current transducer calibration Software controlled Communications TCP IP communications with Campbell A...

Страница 6: ...4 Schematics AeroX Light 4...

Страница 7: ...AeroX Light 5...

Страница 8: ...circuit voltage of the power supply to 18Vdc 5 2 Hardware configuration One AeroX Light can manage four runways that have two lighting loops per runway When the airport has more than four runways add...

Страница 9: ...H1 9 6 3 6 6 6 Black Red Shield none 1 Center S2 H2 9 6 3 5 5 5 Black Red Shield none 2 Edge S3 H3 9 6 3 4 4 4 Black Red Shield none 2 Center S4 H4 10 7 4 6 6 6 Black Red Shield none 3 Edge S5 H5 10 7...

Страница 10: ...g a jumper to set the current range see Figure 5 2 p 8 and Figure 5 3 p 9 The current transducers are set to the 0 to 10 A scale for the 6 6 A LEDs and to the 0 to 20 A scale for the incandescent ligh...

Страница 11: ...e has constants and variables that are set to identify the hardware configuration that matches the runway and sensor configuration The Public Table contains variables that may need to be changed to ma...

Страница 12: ...typical of incandescent light loops Battery Backup 0 or 1 Battery option installed 0 No 1 Yes NOTE The default time allowed for configuration and calibration is one minute If more time is needed chang...

Страница 13: ...Config Port Used setting is Inactive 8 Click the GOES tab and ensure that the GOES Enabled box is not checked 9 Click the Network Services tab and ensure that none of the boxes are checked 10 Click A...

Страница 14: ...nnected after the data is saved and the data logger restarts The new values are automatically updated in the RLIMCalValues constant table and can be restored to the data logger using the Backup and re...

Страница 15: ...rated and press Enter 5 Type the measured Off light level meter reading value in amps in the Low_Current_ Measurement variable and press Enter NOTE Meter reading must be greater than 0 00 Therefore en...

Страница 16: ...CR1000X in the device type window and select the CR1000X Series 4 For Connection Type click Direct Do not check Specify PakBus Address 5 Select Backup Back Up Datalogger to launch the backup function...

Страница 17: ...r using the supplied USB cable 2 Access the Device Configuration Utility software 3 Type CR1000X in the device type window and select the CR1000X Series 4 For Connection Type click Direct Do not check...

Страница 18: ...5 6 RLlM to Aero communication flow AeroX Light 16...

Страница 19: ...ther manufacturer s products that are resold by Campbell Scientific are warranted only to the limits extended by the original manufacturer Refer to www campbellsci com terms warranty for more informat...

Страница 20: ...ion or Repair Reference number contact your CAMPBELL SCIENTIFIC regional office Please write the issued number clearly on the outside of the shipping container and ship as directed For all returns the...

Страница 21: ...rohibit climbing by other persons Take reasonable precautions to secure tripod and tower sites from trespassers l Use only manufacturer recommended parts materials and tools Utility and Electrical l Y...

Страница 22: ...nfo campbellsci fr www campbellsci fr Germany Location Phone Email Website Bremen Germany 49 0 421 460974 0 info campbellsci de www campbellsci de India Location Phone Email Website New Delhi DL India...

Отзывы: