manualshive.com logo in svg
background image

5.3.2 Edit configuration settings

The following procedure uses

Loggernet

,

PC400

, or the

Device Configuration Utility

software. The

configuration settings are changed by editing the Public Table.

1. Change the Update_Configuration variable from false (0) to true (1 or -1).

2. Edit the configuration variables to the values indicated in

Table 5-2

(p. 10). Press Enter after

typing each new value.

3. When all the new values have been entered, change the Update_Complete variable from

false (0) to true (1 or -1). This saves the changes and restarts the data logger.

a. Valid data must be entered in both the Number_Runways and Current_Scale to exit

the calibration routine using the Update_Complete field.

b. Calibration routine can be exited without saving changes by either waiting for the

routine to time out or by changing the CANCEL_Configuration from false (0) to true
(1,-1).

Instructions are provided in the Config_Instruction field and status messages are provided in the
Config_Message variable.

NOTE:
The data logger may need to be reconnected after the data is saved and the data logger
restarts.

The new values are automatically updated in the RLIMCalValues constant table and can be
restored to the data logger using the

Backup and restore

(p. 14) process.

5.4 Current transducer calibration

Calibration of the current transducers and lighting level ensures consistent current measurement
data for the expected current ranges. The calibration routine requires coordination with the light
controller. When prompted, use the light controller to turn off the light loop, then, when
prompted, turn the light loop to highest light level. Each lighting loop is calibrated separately and
may take several minutes to complete.

The calibration routine needs to be done for each runway defined in the configuration.
Calibration on individual light loops can be performed in any order . The runways are assigned a
number starting at number one and have an edge and center light identifier. Each runway
calibration uses the lowest light level and the brightest light level. The low light level must be
entered first, followed by the highest light level. Instructions and feedback are provided in the
Calibration_Instructions and Calibration_Message variables.

AeroX Light

12

Содержание AeroX Light

Страница 1: ...Revision 04 2023 Copyright 2023 Campbell Scientific Inc AeroX Light Runway Light Intensity Monitor RLIM PRODUCT MANUAL...

Страница 2: ...cs 4 5 Configuration 6 5 1 Power configuration 6 5 2 Hardware configuration 6 5 3 Data logger configuration 9 5 3 1 Disable unused services 10 5 3 2 Edit configuration settings 12 5 4 Current transduc...

Страница 3: ...ighting loop using clamp on current transducers Each current transducer outputs from 4 to 20 mA of current proportional to the amount of current in the lighting loop Typically each airport runway has...

Страница 4: ...this manual l Although the AeroX Light is rugged it should be handled as a precision scientific instrument 3 Initial inspection l Upon receipt of the AeroX Light inspect the packaging and contents fo...

Страница 5: ...aintains power to AeroX Light for a minimum of 4 hours Operating temperature 40 to 85 C Clamp on current transducer calibration Software controlled Communications TCP IP communications with Campbell A...

Страница 6: ...4 Schematics AeroX Light 4...

Страница 7: ...AeroX Light 5...

Страница 8: ...circuit voltage of the power supply to 18Vdc 5 2 Hardware configuration One AeroX Light can manage four runways that have two lighting loops per runway When the airport has more than four runways add...

Страница 9: ...H1 9 6 3 6 6 6 Black Red Shield none 1 Center S2 H2 9 6 3 5 5 5 Black Red Shield none 2 Edge S3 H3 9 6 3 4 4 4 Black Red Shield none 2 Center S4 H4 10 7 4 6 6 6 Black Red Shield none 3 Edge S5 H5 10 7...

Страница 10: ...g a jumper to set the current range see Figure 5 2 p 8 and Figure 5 3 p 9 The current transducers are set to the 0 to 10 A scale for the 6 6 A LEDs and to the 0 to 20 A scale for the incandescent ligh...

Страница 11: ...e has constants and variables that are set to identify the hardware configuration that matches the runway and sensor configuration The Public Table contains variables that may need to be changed to ma...

Страница 12: ...typical of incandescent light loops Battery Backup 0 or 1 Battery option installed 0 No 1 Yes NOTE The default time allowed for configuration and calibration is one minute If more time is needed chang...

Страница 13: ...Config Port Used setting is Inactive 8 Click the GOES tab and ensure that the GOES Enabled box is not checked 9 Click the Network Services tab and ensure that none of the boxes are checked 10 Click A...

Страница 14: ...nnected after the data is saved and the data logger restarts The new values are automatically updated in the RLIMCalValues constant table and can be restored to the data logger using the Backup and re...

Страница 15: ...rated and press Enter 5 Type the measured Off light level meter reading value in amps in the Low_Current_ Measurement variable and press Enter NOTE Meter reading must be greater than 0 00 Therefore en...

Страница 16: ...CR1000X in the device type window and select the CR1000X Series 4 For Connection Type click Direct Do not check Specify PakBus Address 5 Select Backup Back Up Datalogger to launch the backup function...

Страница 17: ...r using the supplied USB cable 2 Access the Device Configuration Utility software 3 Type CR1000X in the device type window and select the CR1000X Series 4 For Connection Type click Direct Do not check...

Страница 18: ...5 6 RLlM to Aero communication flow AeroX Light 16...

Страница 19: ...ther manufacturer s products that are resold by Campbell Scientific are warranted only to the limits extended by the original manufacturer Refer to www campbellsci com terms warranty for more informat...

Страница 20: ...ion or Repair Reference number contact your CAMPBELL SCIENTIFIC regional office Please write the issued number clearly on the outside of the shipping container and ship as directed For all returns the...

Страница 21: ...rohibit climbing by other persons Take reasonable precautions to secure tripod and tower sites from trespassers l Use only manufacturer recommended parts materials and tools Utility and Electrical l Y...

Страница 22: ...nfo campbellsci fr www campbellsci fr Germany Location Phone Email Website Bremen Germany 49 0 421 460974 0 info campbellsci de www campbellsci de India Location Phone Email Website New Delhi DL India...

Отзывы: