Installation
Advanced Graphic Data Manager
8
3
Installation
3.1
Incoming acceptance, transport, storage
3.1.1
Incoming acceptance
After receiving the goods, check the following points:
• Is the packaging or the content damaged?
• Is the delivery complete? Compare the goods delivered with what you ordered.
3.1.2
Transport and storage
Observe the following points:
• The unit must be packed in shockproof packaging for storage (and transport). The original
packaging offers the best protection for this.
• The permitted storage temperature is -20 to +60 °C (-4 to 140 °F)
3.2
Installation conditions
Working temperature range:
-10 to 50 °C (22 to 122 °F), max. 75% rel. humidity without condensation.
Impairment of the operating life of the device
To avoid heat accumulation, please always ensure that the unit is sufficiently cooled.
Maintain distance from strong magnetic fields (see Section 10 "Technical data", interference
immunity)
ZPermitted ambient conditions at front: in accordance with unit ingress protection of max. IP65
(with front flap closed)
3.3
Installation instructions
3.3.1
Mounting tool
To install in the control panel, all you need is a screwdriver.