Advanced Graphic Data Manager
Commissioning and use during operation
57
Submenu: Fault mode (only
available in the Expert
setup!)
Settings that lay down how this channel is to react under fault conditions
(e.g. cable open circuit, over range).
Fig. 39:
Setup - Inputs - Universal inputs, Universal input x,
submenu "Fault mode"
Fault switches:
switches the selected relay under fault conditions. The
terminal numbers are shown in brackets.
Picklist:
not used
, relay x (xx-xx)
Note:
If there are several reasons for triggering a relay (e.g. 2 different
limit values), this must be set to "Collective relay" under "Setup ->
Outputs -> Relay -> Relay x".
25000/000 to
25000/039
Save event:
stores a message in the event memory when a fault
condition occurs. Picklist:
no
, yes
25005/000 to
25005/039
Only for "Current" as the signal
and "4-20 mA" as the range
NAMUR NE43:
Switch monitoring of the 4 to 20 mA range as per NAMUR
Recommendation NE43 on and off. The following error ranges apply
when NAMUR NE43 is switched on:
3.8 mA: under range (display shows: vvvvvv)
20.5 mA: overrange (displays shows: ^^^^^^)
3.6 mA or
21.0 mA: cable open circuit (display shows: - - - -)
Picklist:
on
, off
25015/000 to
25015/039
Only for "4-20 mA" or "1-5 V" as
the range and if "NAMUR NE43"
is "on"
Time delay
The system only reacts to a cable open circuit/under range/overrange
(e.g. relay is switched) if this condition is present for the set duration at
least. Factory setting:
0 s
25045/000 to
25045/039
Only for "Voltage" as the signal
and "1-5 V" as the range
Cable open circuit:
Switch cable open circuit detection of the 1-5 V range on or off. If the
cable open circuit detection function is switched on, all values <0.8 V or
>5.2 V are regarded as a cable open circuit (display shows: - - - -)
Picklist:
on
, off
25015/000 to
25015/039
Not available if "Pulse counter" is
the signal!
In the event of an error
Specify the value the unit should continue to use (for calculations) if the
measured value is not valid (e.g. cable open circuit).
Picklist: last valid value, range start, meas. range end, zero
1)
, LOW
1)
,
HIGH
1)
,
value is invalid
, free configuration
25035/000 to
25035/039
Only if "Free configuration" is
selected for "In event of an error"
Error value
The unit continues calculating with this value if a fault occurs. See table
Page 58
25040/000 to
25040/039
Copy settings
Copies settings from actual channel to selected channel. Picklist:
no
, in
universal input x
20115/000 to
20115/039
"Inputs" menu
items
Configurable parameters
(factory settings are highlighted in bold)
Direct access
code