Commissioning and use during operation
Advanced Graphic Data Manager
54
Upper frequency
Only for Signal "Frequency
input"
Specify the upper frequency that corresponds to the end of the
measuring range. A maximum frequency of 12.5 kHz can be configured
here. Factory setting:
1000 Hz
20075/000
to
20075/039
Meas. range end
The same as "Range start". Enter the end value for the measurement
range here, e.g. "14" for a 0-14 pH transmitter.
Note:
Cannot be changed for resistance thermometers and
thermocouples!
20080/000
to
20080/039
Zoom start
If the total transmitter range is not being used then the lower value of
the required range can be entered here (higher resolution). Example:
transmitter 0-14 pH, required range: 5-9 pH. Set up "5" here. The zoom
has no influence on the storage.
20085/000
to
20085/039
Zoom end
As in "Zoom start". Enter the upper value of the required range here.
Example: transmitter 0-14 pH, required range: 5-9 pH. Enter "9" here.
20090/000
to
20090/039
Damping/filter
The more unwanted interference there is on the measurement signal the
higher the value that should be entered here. Result: fast changes will be
damped/suppressed. Factory setting:
0.0 s
20095/000
to
20095/039
Comparison point
Only for Signal "Thermocouples"
Only used when directly connecting thermocouples.
"Internal":
compensation of the voltage error by measuring the
terminal temperature.
"External": compensation of error voltage by using thermostated
comparison points.
Note:
When using thermocouples (TC) with an internal compensation
point and storage cycle of 100 ms the temperature of the compensation
pointing is measured every 5 seconds and the measurement is frozen for
1200 ms by the measurement switchover. This behavior appears only at
the above mentioned set-up and is visible due to the fast 100 ms storage
cycle. E.g. this can be avoided by the use of an external compensation
point.
20100/000
to
20100/039
Comparison temp.
Only for "Comparison point -
external"
Settings for the external comparison temperature (only when connecting
thermocouples directly).
20105/000
to
20105/039
Totalizer
Only for Signal "Pulse counter"
Initial setting for the totalizer. Useful when continuing measurements
recorded to date with an (electro)-mechanical counter.
Factory setting:
0
20300/000
to
20300/039
"Inputs" menu
items
Configurable parameters
(factory settings are highlighted in bold)
Direct access
code