Commissioning and use during operation
Advanced Graphic Data Manager
72
Setup – Outputs, submenu: Relay
"Outputs" menu
items
Configurable parameters
(factory settings are highlighted in bold)
Direct access
code
Submenu: Relay, relay
x
Various relay settings (e.g. operating mode)
The basic version of the unit has 6 relays. 6 additional relays are also available on the optional "Digital card".
Setup for the selected relay:
Fig. 44:
Setup Outputs, submenu: Relay, relay 1
Identifier
User-definable name for the relay.
Factory setting:
relay x
52000/000 to
52000/011
Operating mode
Function of the relay:
"Opening": the relay is closed in the quiescent state (maximum safety).
"Closing":
the relay is open in the quiescent state.
52005/000 to
52005/011
Collective relay
"No": there can only be
one
reason for triggering the relay (if several
trigger factors are assigned, the last trigger factor controls the relay)
"Yes":
the relay can be triggered by
several
factors (e.g. 2 different limit
values) (OR logical operation).
52010/000 to
52010/011
Remote controlled
Specify whether the relay can be controlled remotely (e.g. PC or SMS).
Picklist:
no
, yes
Note:
Remote control by text message (SMS) is only possible for the
"Telealarm" option.
Remote-controlled relays may not be assigned to any other trigger factor
(e.g. limit value alarm).
52015/000 to
52015/011
Содержание LINAX A325
Страница 1: ...Operating instructions Video recorder LINAX A325 ...
Страница 3: ...Advanced Graphic Data Manager 3 ...
Страница 151: ...Advanced Graphic Data Manager Index 151 ...
Страница 152: ...BA00247O 09 en 03 14 71252214 FM10 ...