64
Section 4
MC-III™ Panel Mount Flow Analyzer
Figure 4.28—Two options for configuring a 4-20 mA output
Flow rates in-between the minimum and maximum rate setpoints will result in an output of current between
4 mA and 20 mA according to the following calculation:
=
×
−
+
[
] [
]
MAX
MIN
OUT
CURR
MIN
I
I
I
RATE
Low I
High Low
−
−
Where:
I
OUT
= output current
I
MAX
= maximum current output (20 mA)
I
MIN
= minimum current output (4 mA)
High = programmed flow rate that produces a 20-mA output
Low = programmed flow rate that produces a 4-mA output
RATE
CURR
= flow rate