Section 4
MC-III™ Panel Mount Flow Analyzer
2.
Click File>Discover Modbus
®
Slaves.
3.
Enter a range of addresses you want to search (Figure 4.8).
4.
Enter the baud rate established for network communications.
5.
Adjust the time-out setting, if necessary.
6.
Click “Search.” The software will scan all addresses specified and display all instruments connected.
7.
Click on the appropriate address to connect to a device.
Important: In daisy-chain configurations, verify that each device has a unique slave address.
Figure 4.8—Automatic detection of all connected devices
A user who knows the address of a specific device may also connect to it by clicking File>Connect Device at
Address (Figure 4.9).
Figure 4.9—Slave address selection screen