LEFM 3xxCi User Manual
IB1406 Rev 12
Section 5
Page 28
August 2017
Figure 4.2 User Terminations, Rear View
Note – Conductor insulation for external circuits must be rated for 300V and a minimum temperature of
90ºC.
Power Terminations (Terminal Block 1) – Recommended 16 to 20 AWG wire
2
TB1 contains the power terminations, described below in Figure 4.3 and Figure 4.4.
Table 4.1 Power Terminations
The schematics for the power terminations are shown below in Figure 4.3 and Figure 4.4.
Figure 4.3 DC Power Terminations
2
14 AWG is allowable.
DC Power
TB1, Pin 1
+24 VDC
TB1, Pin 2
(RETURN)
AC Power
TB1, Pin 1 +120/230 VAC
TB1, Pin 2
(RETURN)
Fiber Port
Fiber mode
RJ-45 for
copper mode
TB2, 32 pins
TB1, 2